2007-05-07 15:57:50 | BUILDING PLAN REVIEW |
| PERMIT: 07040753 |
| ADD: 1720 CENTREPARK DR. E |
| CONT: THE WEITZ CO, LLC. |
| TEL: (561)686-5511 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| 2)110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PROJECT WAS DESIGNED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| ) NUMBER OF FLOORS |
| ) NUMBER OF ROOMS |
| ) SQ. FT. FOOTPRINT |
| ) SQ. FT. UNDER ROOF (TOTAL) |
| ) OCCUPANT LOAD |
| |
| 3)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 4)THE DOOR ELEVATION ON SHEET A2.01 SHOWS A 3' X 7' |
| DOOR, HOWEVER THE FLOOR PLAN SHOWS 3' X 8' DOORS. |
| CLARIFY. |
| |
| 5)WHERE IS THE FOURTH 8'-8" PARTITION WALL LOCATED? |
| THERE ARE THREE SECTIONS SHOWN ON THE PLANS, INDICATE |
| WHERE THE OTHER WALL IS. |
| |
| 6)THE TITLE BLOCK IS MISSING THE PRINTED NAME AND |
| LICENSE NUMBER OF THE ARCHITECT OF RECORD. THE DATE ON |
| THE SEAL IS NOT LEGIBLE. SEE F.A.C.61G1-16.004. |
| |
| 7)IF THERE IS A SOFFIT AT THE PERIMETER OF THE |
| ACOUSTICAL TILE CEILING IN THE OPEN WORKSTATION AREA, |
| PROVIDE THE WALL DETAIL FOR THAT SOFFIT. ALSO PROVIDE |
| SOME ELEVATION DETAILS OF THE PROJECT. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. |
| FBC. 106.1.1.(SEE ALSO SEC. 106.3.5). |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |
| |
| |