Plan Review Notes
Plan Review Notes For Permit 07040753
Permit Number 07040753
Review Stop B
Sequence Number 1
Notes
Date Text
2007-05-07 15:57:50BUILDING PLAN REVIEW
 PERMIT: 07040753
 ADD: 1720 CENTREPARK DR. E
 CONT: THE WEITZ CO, LLC.
 TEL: (561)686-5511
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)THE DOOR ELEVATION ON SHEET A2.01 SHOWS A 3' X 7'
 DOOR, HOWEVER THE FLOOR PLAN SHOWS 3' X 8' DOORS.
 CLARIFY.
  
 5)WHERE IS THE FOURTH 8'-8" PARTITION WALL LOCATED?
 THERE ARE THREE SECTIONS SHOWN ON THE PLANS, INDICATE
 WHERE THE OTHER WALL IS.
  
 6)THE TITLE BLOCK IS MISSING THE PRINTED NAME AND
 LICENSE NUMBER OF THE ARCHITECT OF RECORD. THE DATE ON
 THE SEAL IS NOT LEGIBLE. SEE F.A.C.61G1-16.004.
  
 7)IF THERE IS A SOFFIT AT THE PERIMETER OF THE
 ACOUSTICAL TILE CEILING IN THE OPEN WORKSTATION AREA,
 PROVIDE THE WALL DETAIL FOR THAT SOFFIT. ALSO PROVIDE
 SOME ELEVATION DETAILS OF THE PROJECT. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED.
 FBC. 106.1.1.(SEE ALSO SEC. 106.3.5).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  