2007-11-30 11:21:53 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED 3RD TIME: |
| |
| ***** FROM PREVIOUS REVIEW***** |
| |
| 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, |
| DEPT. OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD |
| SERVICE LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE |
| CITY FOR REVIEW. AMINIMUM OF TWO SETS OF PLANS WITH |
| REVIEW STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" |
| ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR |
| REVIEW. SECTION 102.2.1. |
| *****RESPONSE NOTED: HOWEVER THE RESUBMITTED PLANS DO |
| NOT HAVE THE TWO PAGE "WORKSHEETS" ATTACHED TO THE |
| STAMPED DBPR PLAN SHEET. THESE TWO PAGE WORKSHEETS ARE |
| REQUIRED. |
| |
| 2. PER MUNICIPAL CODE ARTICLE III SECTION 90-124, |
| THE EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED |
| AND LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| (561) 822-2272, E-MAIL: [email protected] OR CLAVIN |
| WILLIAMS, PHONE: (561) 822-2284, E-MAIL: |
| [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| NOTE: WRITTEN APPROVAL IS REQUIRED OF THE |
| EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL |
| COMPLIANCE BEFORE A PERMIT CAN BE ISSUED. |
| *****REPONSE NOTED: HOWEVER APPROVAL OF THE INTERCEPTOR |
| SIZE AND LOCATION IS REQUIRED FROM ENVIRONMENTAL |
| COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO |
| OR MR. WILLIAMS. PERMIT WILL NOT BE ISSUED WITHOUT |
| ENVIRONMENTAL COMPLIANCE APPROVAL SHEET. |
| |
| 3. OK |
| |
| 4. OK |
| |
| 5. OK |
| |
| 6. OK |
| |
| 7. OK |
| |
| 8. OK |
| |
| 9. OK (REMOVED FROM NOTES) HOWEVER APPROVAL OF THE |
| SIZE AND LOCATION STILL REQUIRED FROM EVIRONMENTAL |
| COMPLIANCE, REFERENCE COMMENT #2. |
| |
| 10. OK |
| |
| 11. OK, NOTE: FLORIDA PUBLIC UTILITIES CO. HAS A |
| SEPERATE PERMIT FOR THE GAS PIPING SYSTEM PERMIT |
| #07080547. |
| |
| **********NEW COMMENTS********** |
| |
| 1B & 2B. OK, WATER HEATER IS EXISTING. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |