Plan Review Notes
Plan Review Notes For Permit 07040733
Permit Number 07040733
Review Stop P
Sequence Number 3
Notes
Date Text
2007-11-30 11:21:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 ***** FROM PREVIOUS REVIEW*****
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT. OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD
 SERVICE LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE
 CITY FOR REVIEW. AMINIMUM OF TWO SETS OF PLANS WITH
 REVIEW STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS"
 ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR
 REVIEW. SECTION 102.2.1.
 *****RESPONSE NOTED: HOWEVER THE RESUBMITTED PLANS DO
 NOT HAVE THE TWO PAGE "WORKSHEETS" ATTACHED TO THE
 STAMPED DBPR PLAN SHEET. THESE TWO PAGE WORKSHEETS ARE
 REQUIRED.
  
 2. PER MUNICIPAL CODE ARTICLE III SECTION 90-124,
 THE EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED
 AND LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE:
 (561) 822-2272, E-MAIL: [email protected] OR CLAVIN
 WILLIAMS, PHONE: (561) 822-2284, E-MAIL:
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 NOTE: WRITTEN APPROVAL IS REQUIRED OF THE
 EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL
 COMPLIANCE BEFORE A PERMIT CAN BE ISSUED.
 *****REPONSE NOTED: HOWEVER APPROVAL OF THE INTERCEPTOR
 SIZE AND LOCATION IS REQUIRED FROM ENVIRONMENTAL
 COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO
 OR MR. WILLIAMS. PERMIT WILL NOT BE ISSUED WITHOUT
 ENVIRONMENTAL COMPLIANCE APPROVAL SHEET.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK (REMOVED FROM NOTES) HOWEVER APPROVAL OF THE
 SIZE AND LOCATION STILL REQUIRED FROM EVIRONMENTAL
 COMPLIANCE, REFERENCE COMMENT #2.
  
 10. OK
  
 11. OK, NOTE: FLORIDA PUBLIC UTILITIES CO. HAS A
 SEPERATE PERMIT FOR THE GAS PIPING SYSTEM PERMIT
 #07080547.
  
 **********NEW COMMENTS**********
  
 1B & 2B. OK, WATER HEATER IS EXISTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]