Date |
Text |
2007-09-21 10:20:23 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| CITY WPB MUNICIPAL CODE |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. |
| OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD SERVICE |
| LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE CITY |
| FOR REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH REVIEW |
| STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" |
| ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR |
| REVIEW. SECTION 102.2.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 2. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. |
| PLEASE CONTACE RODNEY COMPO, (561) 822-2272 OR CALVIN |
| WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561) |
| 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected] |
| AND [email protected]. MUNICIPAL CODE ARTICLE III |
| SECTION 90-124. |
| ****RESPONSE NOTED, BUT APPROVAL OF INTERCEPTOR SIZE |
| SHALL BE FROM INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO |
| OR MR. WILLIAMS. |
| |
| 3. OK |
| |
| 4. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, |
| PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE |
| THROUGH AN INDIRCET WASTE PIPE BY MEANS OF AN AIR GAP. |
| SECTION 802.1. SEE THE THREE COMPARTMENT SINK AND THE |
| TWO COMPARTMENT SINK. A FLOOR SINK SHALL BE REQUIRED. |
| SECTION 802.3. |
| ****RESPONSE NOTED, BUT THE TWO COMPARTMENT SINK SHOWS |
| A FLOOR DRAIN AS THE INDIRECT WASTE RECEPTOR. FLOOR |
| DRAINS ARE NOT APPROVED WASTE RECEPTORS PER SECTION |
| 802.3. A FLOOR SINK IS REQUIRED. PLEASE CHANGE FIXTURE |
| ON PLANS & NOTES. |
| |
| 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| VALVES, AND WATER HAMMER ARRESTORS REQUIRED FOR QUICK |
| CLOSING VALVES. WATER HAMMER ARRESTORS SHALL BE LOCATED |
| NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE |
| CEILING. PDI-WH 201 AND MANUF. INSTALLATION |
| INSTRUCTIONS. SECTION 106.3.5.1.3(3)(10)(13). |
| ****RESPONSE NOTE, BUT NO RISER DIAGRAMS WERE SUBMITTED |
| SHOWING THE PIPING TO THE NEW FIXTURES. |
| |
| 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO |
| THE RESTAURANT. SECTION 608.13.2. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 7. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION |
| 607.3.1. PLEASE INDICATE METHOD. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 8. OK |
| |
| 9. SHT A-1 CODE REVIEW NOTES CONCERNING GREASE |
| INTERCEPTORS. THE WEST PALM BEACH MUNICIPAL CODE, |
| ARTICLE III SECTION 90-124(7)(A THRU G) SHALL GOVERN |
| THE INSTALLATION, TYPE, MANITENANCE ETC OF THE GREASE |
| INTERCEPTOR. SEE ATTACHED SHEET FOR REQUIREMENTS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 10. SHT A-2 PLUMBING GENERAL NOTES #4. SUBMIT A |
| CONDENSATE RISER DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, |
| VENTS AND INDICATE THE TERMINATION POINT. SECTION |
| 106.3.5.1.3(13).--NOTE #6PVC PIPEIS NOT ALLOWED |
| FOR DISTRIBUTION PIPE PER TABLE 605.4.--NOTE #8 AIR |
| CHAMBERS ARE NOT APPROVED. PDI-WH 201 AND SECTION |
| 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR ALL |
| QUICK CLOSING VALVES. |
| ****NO RESPONSE, NOT ADDRESSED FOR GENERAL NOTES #4 & |
| #8. NOTE #6 IS OK. |
| |
| 11. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES. |
| A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE |
| FOLLOWING INFORMATION FOR THE GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| H. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| I. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| ****NO RESPONSE FOR ALL GAS REQUIREMENTS, COMMENTS NOT |
| ADDRESSED. INFORMATION NOW SHOWN ON SHEET E-1. |
| |
| **********NEW COMMENTS********** |
| |
| 1B. THE ENERGY CALCULATIONS ARE INCOMPLETE. PLEASE |
| INDICATE THE SYSTEMS INFORMATION FOR THE WATER HEATER. |
| SECTION 13-103. |
| |
| 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) AND |
| THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE ONLY |
| AT THIS TIME. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |