Plan Review Notes
Plan Review Notes For Permit 07040733
Permit Number 07040733
Review Stop M
Sequence Number 2
Notes
Date Text
2007-09-07 14:29:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 *** EXISTING RESTAURANT NEW OFFICE BEING INCLOSED AND
 NEW KITCHEN HOOD NOTES TO BE ADJUSTED. ***
  
 1) PLANS MUST SHOW THAT KITCHEN EXHAUST HOODS ARE BEING
 INSTALLED TO COMPLY WITH MECH. 507.2. SHOW LOCATION OF
 HOODS, TYPE OF HOODS, SIZE OF HOODS, EXHAUST AND
 MAKE-UP AIR CFM'S. (ENGINEERING FOR HOODS MAY BE
 SUBMITTED WHEN APPLYING FOR HOOD PERMIT).
  
 2) PROVIDE OUT-SIDE AIR CALCULATIONS, SEE MECH.401.2.
  
 3) PROVIDE AIR BALANCE CALCULATIONS TO SHOW COMPLIANCE
 WITH FBC 13-409.1.ABC.3.6.1.
  
 4) THE OFFICE WILL REQUIRE RETURN AIR, SEE MECH.
 601.4.
  
 5) THE RESPONSE LETTER SUBMITTED BY NELSON MARIN STATES
 (THESE FACTORS ARE CONSIDERED IN THE ENERGY
 CALCULATIONS SUBMITTED WITH THESE DRAWINGS). AS THE
 ENERGY CAL'S ARE ON FORM C THEY SHOW NO CALCULATIONS OR
 CONSIDERATIONS. PLEASE SUBMIT THE CALCULATIONS THAT YOU
 ARE REFERRING TO.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]