Plan Review Notes For Permit 07040733 |
Permit Number |
07040733 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-09-07 14:29:49 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | *** EXISTING RESTAURANT NEW OFFICE BEING INCLOSED AND | | NEW KITCHEN HOOD NOTES TO BE ADJUSTED. *** | | | | 1) PLANS MUST SHOW THAT KITCHEN EXHAUST HOODS ARE BEING | | INSTALLED TO COMPLY WITH MECH. 507.2. SHOW LOCATION OF | | HOODS, TYPE OF HOODS, SIZE OF HOODS, EXHAUST AND | | MAKE-UP AIR CFM'S. (ENGINEERING FOR HOODS MAY BE | | SUBMITTED WHEN APPLYING FOR HOOD PERMIT). | | | | 2) PROVIDE OUT-SIDE AIR CALCULATIONS, SEE MECH.401.2. | | | | 3) PROVIDE AIR BALANCE CALCULATIONS TO SHOW COMPLIANCE | | WITH FBC 13-409.1.ABC.3.6.1. | | | | 4) THE OFFICE WILL REQUIRE RETURN AIR, SEE MECH. | | 601.4. | | | | 5) THE RESPONSE LETTER SUBMITTED BY NELSON MARIN STATES | | (THESE FACTORS ARE CONSIDERED IN THE ENERGY | | CALCULATIONS SUBMITTED WITH THESE DRAWINGS). AS THE | | ENERGY CAL'S ARE ON FORM C THEY SHOW NO CALCULATIONS OR | | CONSIDERATIONS. PLEASE SUBMIT THE CALCULATIONS THAT YOU | | ARE REFERRING TO. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|