2007-09-05 19:13:08 | ** DENIED 2ND REVIEW ** |
| |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| WORK SHALL INCLUDE ALL LABOR, ALL MATERIALS, ALL |
| PERMANENTLY INSTALLED EQUIPMENT, ARCHITECTURAL AND |
| DESIGN FEES ETC. |
| PLEASE SEE THE ELECTRICAL SCOPE OF WORK AS ORIGINALLY |
| SHOWN HAS SUBSTANTIALLY INCREASED ALONE. |
| PLEASE MAKE ADJUSTMENTS OR A VALUE WILL BE APPLIED |
| USING GUIDES ADOPTED UNDER THE FBC AND ADOPTED |
| REFERENCE BOOKS. |
| |
| 2) NOTE: PLEASE SEE THE NEW ENERGY CALCULATIONS |
| SUBMITTED ARE NOT COMPLETE. PLEASE SEE THE LIGHTING |
| DENSITIES ARE SHOWN BLANK. |
| PLEASE SEE THE SIGNATURE NOT THE TYPED NAME OF PERSON |
| PREPARING DOCUMENT IS REQUIRED. 13-103.1.1.1 |
| PLEASE SEE THE ENGINEER OF RECORD AS LISTED IS NOT |
| SIGN, DATED AND SEALED. FBC 13-103.1.1.1, FAC |
| 61G15-23.002, FS 471.025 |
| PLEASE SEE THE OWNER AGENT IS BLANK. |
| FBC 13-415.1.C |
| |
| ** ELECTRICAL PLANS ARE IN GOOD SHAPE AS THE ENGINEER |
| DID A GOOD JOB ADDRESSING THE ELECTRICAL COMMENTS. WELL |
| DONE. |
| |
| ** PLEASE ADDRESS COMMENTS #1 AND #2. THE ELECTRICAL |
| SHEETS WILL BE STAMPED AT THIS TIME. |
| |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |