Plan Review Notes For Permit 07040733 |
Permit Number |
07040733 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-25 15:48:06 | *****DENIED***** | | | | | | 1.ON THE COVER SHEET, REFERENCE THE 2003 EDITION OF | | NFPA 101. | | | | 2.PLEASE INDICATE IF THIS IS A CHANGE OF OCCUPANCY. | | | | 3.INDICATE IF THE BUILDING/TENANT SPACE IS FIRE | | SPRINKLERED AND/OR HAS A FIRE ALARM.IF THE SCOPE OF | | WORK HAS CAUSE FOR ANY OF THESE SYSTEMS TO BE | | REMODELED, SEPARATE PLANS AND PERMIT WILL BE REQUIRED. | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 6.THE REMOVAL AND/OR THE STOCKING OF BUILDING | | MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | THEREOF (INCLUDING STREETS,ROADS, FIRE LANES). | | | | 7.PROVIDE A T LEAST ONE 2A:10BC RATED FIRE | | EXTINGUISHER IN THE NON COOKING AREA. | | | | 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR WALLS AND | | CEILINGS IN THE EXITS, EXIT AISLE CORRIDORS AND OTHER | | SPACES. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | 2007-06-25 15:15:30 | ***** |
|