Plan Review Notes
Plan Review Notes For Permit 07040733
Permit Number 07040733
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-27 16:35:49** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE SEE THE VALUE FOR SCOPE OF WORK SHALL
 INCLUDE ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY
 OF THESE ARE OWNER SUPPLIED.
 PLEASE SEE THE VALUE IS LOW AT THIS TIME AND WILL NEED
 TO BE ADJUSTED.
 PLEASE THAT A VALUE MAY BE ASSESSED BY USING GUIDES AS
 ADOPTED BY THE FBC. 108.3
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 ** PLEASE SEE THE INCORRECT NEC IS NOTED.
  
 3) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING
 CONTROLS BEING INSTALLED. PLEASE PROVIDE DETAIL ON
 OCCUPANCY DEVICE AND PLEASE SEE SOME AREAS LIKE THE
 KITCHEN IN WHICH THE SINGLE WALL WHICH AT LOCATION
 SHOWN MAY NOT PROVIDE THE NEEDED COVERAGE.
 PLEASE DETAIL THE CONNECTION IN BAR AREA AND ALL OTHER
 AREAS.
 PLEASE SEE THE EXISTING BATH ROOMS WILL REQUIRE
 DEVICES.
 PLEASE SEE NOT ALL AREAS INDICATE LIGHTING POWER
 DENSITIES.
 PLEASE SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE.
 PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETED WITH ALL
 FIXTURE TYPES, WATTAGES ETC. (THESE MAY BE REVISED AT A
 LATER DATE IF CHANGED).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3,
 13-415.1.AB.1.1, 13-415.2 ETC.
  
 4) NOTE: PLEASE INDICATE ALL RECEPTACLES SERVING
 KITCHEN AREAS AS GFI. MOST ARE DONE AND ONLY ONE IS
 MISSING IN THIS DESIGNATED AREA.
 PLEASE ALSO SEE ONLY MISPRINT FOR THE CODE SECTION AS
 NOTED IN GENERAL ELECTRICAL NOTES.
 PLEASE SEE 210.8B3.
  
 5) NOTE: PLEASE SEE ELECTRICAL SHEETS IN TWO OF THE
 SETS ARE INSERTED UPSIDE DOWN, BACKWARDS AND THERE ARE
 MORE SHEETS THAN SHOULD BE IN SETS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND INSERT NEW
 SHEETS INTO COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE BE SURE TO CHECK THE SHEETS.
 PLEASE ONLY SUBMIT ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS.
 ** PLEASE BE CAREFUL NOT TO DISCARD ANY SHEETS STAMP BY
 THE DIVISION OF HOTELS ETC).
  
 6) NOTE: PLEASE INDICATE IF THE PANELS CONTAIN
 FEED-THRU LUGS OR IS THERE OVER CURRENT PROTECTION FROM
 ONE TO THE OTHER?
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE LOADS AS SHOWN ON PANEL *A* IS
 LOWER THAN THE LOAD ON LOAD CALCULATIONS.THIS IS NOT
 POSSIBLE WHEN PANEL USUALLY SHOW THE CONNECTED LOAD OR
 THE SAME DE-RATED LOAD AS FIGURED IN THE LOAD
 CALCULATIONS.
 PLEASE COORDINATE THESE.
 FBC 106.1.2
 NEC 220
  
 8) NOTE: PLEASE SEE 422.13 AS THIS WAS REVISED IN THE
 2005 CODE TO REQUIRE ALL ELECTRIC WATER HEATER LOADS TO
 BE SHOWN AND DONE AT 125%.
  
 9) NOTE: PLEASE INDICATE THE EXISTING LIGHTING FIXTURES
 IN THE BATHROOMS.
  
 10) NOTE: PLEASE SEE THE TITLE COVER SHEET INDICATES
 PLANS SUBMITTED BY MARTEK, YET NO MECHANICAL PLANS WERE
 SUBMITTED FOR REVIEW? PLEASE VERIFY.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE OR REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]