2007-04-27 16:35:49 | ** UNSAT ** |
| |
| ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| 1) NOTE:PLEASE SEE THE VALUE FOR SCOPE OF WORK SHALL |
| INCLUDE ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY |
| OF THESE ARE OWNER SUPPLIED. |
| PLEASE SEE THE VALUE IS LOW AT THIS TIME AND WILL NEED |
| TO BE ADJUSTED. |
| PLEASE THAT A VALUE MAY BE ASSESSED BY USING GUIDES AS |
| ADOPTED BY THE FBC. 108.3 |
| |
| 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| ** PLEASE SEE THE INCORRECT NEC IS NOTED. |
| |
| 3) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING |
| CONTROLS BEING INSTALLED. PLEASE PROVIDE DETAIL ON |
| OCCUPANCY DEVICE AND PLEASE SEE SOME AREAS LIKE THE |
| KITCHEN IN WHICH THE SINGLE WALL WHICH AT LOCATION |
| SHOWN MAY NOT PROVIDE THE NEEDED COVERAGE. |
| PLEASE DETAIL THE CONNECTION IN BAR AREA AND ALL OTHER |
| AREAS. |
| PLEASE SEE THE EXISTING BATH ROOMS WILL REQUIRE |
| DEVICES. |
| PLEASE SEE NOT ALL AREAS INDICATE LIGHTING POWER |
| DENSITIES. |
| PLEASE SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE. |
| PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETED WITH ALL |
| FIXTURE TYPES, WATTAGES ETC. (THESE MAY BE REVISED AT A |
| LATER DATE IF CHANGED). |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3, |
| 13-415.1.AB.1.1, 13-415.2 ETC. |
| |
| 4) NOTE: PLEASE INDICATE ALL RECEPTACLES SERVING |
| KITCHEN AREAS AS GFI. MOST ARE DONE AND ONLY ONE IS |
| MISSING IN THIS DESIGNATED AREA. |
| PLEASE ALSO SEE ONLY MISPRINT FOR THE CODE SECTION AS |
| NOTED IN GENERAL ELECTRICAL NOTES. |
| PLEASE SEE 210.8B3. |
| |
| 5) NOTE: PLEASE SEE ELECTRICAL SHEETS IN TWO OF THE |
| SETS ARE INSERTED UPSIDE DOWN, BACKWARDS AND THERE ARE |
| MORE SHEETS THAN SHOULD BE IN SETS. |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND INSERT NEW |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE BE SURE TO CHECK THE SHEETS. |
| PLEASE ONLY SUBMIT ONE COPY OF THE OLD/VOIDED REMOVED |
| SHEETS. |
| ** PLEASE BE CAREFUL NOT TO DISCARD ANY SHEETS STAMP BY |
| THE DIVISION OF HOTELS ETC). |
| |
| 6) NOTE: PLEASE INDICATE IF THE PANELS CONTAIN |
| FEED-THRU LUGS OR IS THERE OVER CURRENT PROTECTION FROM |
| ONE TO THE OTHER? |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE SEE THE LOADS AS SHOWN ON PANEL *A* IS |
| LOWER THAN THE LOAD ON LOAD CALCULATIONS.THIS IS NOT |
| POSSIBLE WHEN PANEL USUALLY SHOW THE CONNECTED LOAD OR |
| THE SAME DE-RATED LOAD AS FIGURED IN THE LOAD |
| CALCULATIONS. |
| PLEASE COORDINATE THESE. |
| FBC 106.1.2 |
| NEC 220 |
| |
| 8) NOTE: PLEASE SEE 422.13 AS THIS WAS REVISED IN THE |
| 2005 CODE TO REQUIRE ALL ELECTRIC WATER HEATER LOADS TO |
| BE SHOWN AND DONE AT 125%. |
| |
| 9) NOTE: PLEASE INDICATE THE EXISTING LIGHTING FIXTURES |
| IN THE BATHROOMS. |
| |
| 10) NOTE: PLEASE SEE THE TITLE COVER SHEET INDICATES |
| PLANS SUBMITTED BY MARTEK, YET NO MECHANICAL PLANS WERE |
| SUBMITTED FOR REVIEW? PLEASE VERIFY. |
| |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE OR REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |