2008-12-02 10:53:22 
  
 REVISION DENIED
  
 THE PERMIT SET OF PLANS WERE ISSUED UNDER PROVISO'S TO
 BE CORRECTED ON THE FIRST REVISION. THE FOLLOWING HAVE
 NOT BEEN CORRECTED ON THE ELECTRICAL PLAN SHEET E2.
  
 1} BATH CIRCUITS PER 210.11(C)(3)*** BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS.***CIRCUIT #10 LABELED "FLORIDA ROOM
 RECEPTACLES" SERVE THE BATH RECEPTACLES IN VIOLATION OF
 THIS ARTICLE. INDICATE BATH CIRCUIT ON THE PANEL
 SCHEDULE PER 408.4.
  
 2} .R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** THE
 NOTE (#9) REQUIRING THAT ARTICLE WAS REMOVED FROM THE
 PLAN. ALSO SEE THAT EACH SMOKE ALARM (MISMARKED
 "DETECTORS") IS ON A DIFFERENT CIRCUIT THEREFORE NOT
 INTERCONNECTED PER MANUFACTURE SPECIFICATION.
  
 NEW COMMENT:
  
 3} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. PER 481.229(1)(B) JOSEPH
 DRAGONMUST MAKE ANY CHANGES TO THIS SHEET.
  
 NOTE: THE PANEL LOCATION SUBMITTED IS CODE COMPLIANT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  
  