2008-12-02 10:53:22 | |
| |
| REVISION DENIED |
| |
| THE PERMIT SET OF PLANS WERE ISSUED UNDER PROVISO'S TO |
| BE CORRECTED ON THE FIRST REVISION. THE FOLLOWING HAVE |
| NOT BEEN CORRECTED ON THE ELECTRICAL PLAN SHEET E2. |
| |
| 1} BATH CIRCUITS PER 210.11(C)(3)*** BATHROOM BRANCH |
| CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| NO OTHER OUTLETS.***CIRCUIT #10 LABELED "FLORIDA ROOM |
| RECEPTACLES" SERVE THE BATH RECEPTACLES IN VIOLATION OF |
| THIS ARTICLE. INDICATE BATH CIRCUIT ON THE PANEL |
| SCHEDULE PER 408.4. |
| |
| 2} .R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** THE |
| NOTE (#9) REQUIRING THAT ARTICLE WAS REMOVED FROM THE |
| PLAN. ALSO SEE THAT EACH SMOKE ALARM (MISMARKED |
| "DETECTORS") IS ON A DIFFERENT CIRCUIT THEREFORE NOT |
| INTERCONNECTED PER MANUFACTURE SPECIFICATION. |
| |
| NEW COMMENT: |
| |
| 3} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED |
| TO REVISE HIS/HER PLAN. PER 481.229(1)(B) JOSEPH |
| DRAGONMUST MAKE ANY CHANGES TO THIS SHEET. |
| |
| NOTE: THE PANEL LOCATION SUBMITTED IS CODE COMPLIANT. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |