2008-05-22 11:04:32 | PLUMBING PLAN REVIEW: |
| DENIED **2ND TIME: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| COMMENTS WILL FOLLOW THE PREVIOUS REVIEW COMMENTS. |
| **NOTE: NO COMMENT RESPONSE FROM DESIGNER. |
| |
| 1. SHEET D3, SANITARY ISOMETRIC RISER DOES NOT REFLECT |
| THE FLOOR PLAN OF SHEET F1 AND IS NOT CODE COMPLIANT. |
| PROVIDE THE FLAT PLAN SANITARY UNDERGROUND PLUMBING |
| LAYOUT ON SHEET F1 AND REFLECT THAT ON THE RESUBMITTED |
| SANITARY ISOMETRIC. PER FBC PLUMBING SECTION 701.1 |
| SCOPE. |
| |
| **THE RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM ON |
| SHEET D-3 STILL DOES NOT REFLECT THE FLOOR PLAN OF |
| SHEET F1. THE WASTE AND VENT PIPING FOR THE BATHTUB IS |
| MISSING ON THE RESUBMITTED ISOMETRIC AND THE FLOOR |
| PLAN. THE WASHING MACHINE AND BIDET DO NOT REFLECT THE |
| FLOOR PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS |
| ON SHEETS F1 AND D-3. PER FBC PLUMBING SECTION 701.1 |
| SCOPE. |
| |
| 2. "OK" COMMENT ADDRESSED. |
| |
| 3. "OK" COMMENT ADDRESSED. |
| |
| **THE FOLLOWING ARE NEW COMMENTS** |
| |
| 4. SHEET D3 THE BIDET NEEDS A VENT. PER FBC-2004 |
| PLUMBING TABLE 906.1. THE MAXIMUM DISTANCE FOR 2 INCH |
| TRAP FROM A VENT IS 6 FEET. |
| |
| 5. SHEET D3 THE WATER CLOSET DOES NOT REQUIRE A TRAP |
| DO TO THE FACT IT HAS AN INTEGRAL TRAP. A FIXTURE SHALL |
| NOT BE DOUBLE TRAPPED. PER FBC-2004 PLUMBING SECTION |
| 1002.1 FIXTURE TRAPS. |
| |
| 6. SHEET D3 THE RESUBMITTED SANITARY ISOMETRIC IS NOT |
| SIZING ALL TRAPS. PER (W.P.B. AS AMENDED) SECTION |
| 106.3.5.4 RESIDENTIAL (9) PLUMBING. |
| |
| 7. SHEET D3 THE RESUBMITTED SANITARY ISOMETRIC IS |
| INCORRECTLY INDICATING CLEANOUT LOCATIONS OR NOT |
| INDICATING THEM AT ALL PER THE FOLLOWING FBC-2004 |
| PLUMBING SECTIONS. |
| |
| (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| SHALL BE PROVIDED AT THE BASE OF EACH |
| WASTE OR SOIL STACK. |
| **INCORRECTLY INDICATED ON PLANS. |
| |
| (B) 708.3.5 BUILDING DRAIN AND BUILDING |
| SEWER JUNCTION. THERE SHALL BE A TWO-WAY |
| CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. |
| **MISSING FROM PLANS |
| |
| (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| BE THE SAME NOMINAL SIZE AS THE PIPE |
| THEY SERVE UP TO 4 INCHES (102MM). |
| NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 |
| INCH. |
| **MISSING FROM PLANS. |
| |
| (D) 708.9 ACCESS. ACCESS SHALL BE |
| PROVIDED TO ALL CLEANOUTS. |
| NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| LOCATED 4' A.F.F. |
| **MISSING FROM PLANS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |