2008-02-29 16:13:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET D3, SANITARY ISOMETRIC RISER DOES NOT REFLECT
 THE FLOOR PLAN OF SHEET F1 AND IS NOT CODE COMPLIANT.
 PROVIDE THE FLAT PLAN SANITARY UNDERGROUND PLUMBING
 LAYOUT ON SHEET F1 AND REFLECT THAT ON THE RESUBMITTED
 SANITARY ISOMETRIC. PER FBC PLUMBING SECTION 701.1
 SCOPE.
  
 2. SHEET D3 SANITARY ISOMETRIC RISER DIAGRAM THE BAR
 SINK IS MISSING FROM THE RISER DIAGRAM. PER FBC
 PLUMBING SECTION 701.1 SCOPE.
  
 3. THE WASHING MACHINE CAN NOT DRAIN INTO THE WET
 VENTED BATHROOM GROUP. THE WASHING MACHINE MUST DRAIN
 DOWN STREAM OF THE BATHROOM GROUP. PER FBC PLUMBING
 SECTION 909.1 WET VENT PERMITTED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  