2008-02-29 16:13:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET D3, SANITARY ISOMETRIC RISER DOES NOT REFLECT |
| THE FLOOR PLAN OF SHEET F1 AND IS NOT CODE COMPLIANT. |
| PROVIDE THE FLAT PLAN SANITARY UNDERGROUND PLUMBING |
| LAYOUT ON SHEET F1 AND REFLECT THAT ON THE RESUBMITTED |
| SANITARY ISOMETRIC. PER FBC PLUMBING SECTION 701.1 |
| SCOPE. |
| |
| 2. SHEET D3 SANITARY ISOMETRIC RISER DIAGRAM THE BAR |
| SINK IS MISSING FROM THE RISER DIAGRAM. PER FBC |
| PLUMBING SECTION 701.1 SCOPE. |
| |
| 3. THE WASHING MACHINE CAN NOT DRAIN INTO THE WET |
| VENTED BATHROOM GROUP. THE WASHING MACHINE MUST DRAIN |
| DOWN STREAM OF THE BATHROOM GROUP. PER FBC PLUMBING |
| SECTION 909.1 WET VENT PERMITTED. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |