2007-05-11 09:58:03 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE VERIFY THE CONFIGURATION OF THE METER AND |
| DISCONNECTS SHOWN. THEY WOULD APPEAR TO BE A |
| METER/MAIN, RATHER THAN SEPARATE DISCONNECTS AS NOTED. |
| CORRECT THE RISER. |
| |
| 2} PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL |
| SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230 |
| CAN BE REVIEWED. THE "PROPOSED 100 AMP" PANEL MAY BE |
| REQUIREED TO BE GROUNDED PER 250.32 AND HAVE A MAIN PER |
| 225.31, DEPENDING ON LOCATION. |
| |
| 4 } 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN |
| ELECTRODE ENCASED BY AT LEAST 50 MM (2 IN.) OF |
| CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF A |
| CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT |
| CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 6.0 M |
| (20 FT) OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER |
| ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS |
| OR RODS OF NOT LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, |
| OR CONSISTING OF AT LEAST 6.0 M (20 FT) OF BARE COPPER |
| CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS |
| SHALL BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL |
| STEEL TIE WIRES OR OTHER EFFECTIVE MEANS. THIS IS |
| AVAILABLE GIVEN A FOOTER IS BEING POURED. PLEASE ADD TO |
| RISER. |
| |
| 5} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 |
| FLORIDA ADMINISTRATIVE CODE. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |