2007-06-12 17:54:04 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*. FEES ARE DUE FOR THE STATE RADON AND
 THE INCREASED PERMIT VALUE IN THE AMOUNT OF $ 241.32
 THIS MUST BE PAID BEFORE FURTHER PLAN REVIEW IS MADE.
  
 4)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 5)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. PLEASE SEE THAT
 FOUNDATION PLAN HAS AN OUT TO OUT MEASUREMENT OF 17'-2"
 AND THE TRUSS ENGINEERING STATES 18'-2"ALSO PER
 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 6)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 7)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 8)PLEASE CORRECT THE DISCREPANCY BETWEEN THE
 FOUNDATION PLAN OVERALL MEASUREMENT OF 52'-0" AND THE
 FLOOR PLAN OF 51'-11"
  
 9)TRUSS LAYOUT ON T/1 HAS NOTES FOR MARK "C" THAT
 CALL FOR META12 STRAPS BUT THE UPLIFT TABLE HAS TYPE D
 WHICH IS A HETA20. THE META12 DOES NOT MEET THE UPLIFT
 VALUE FROM THE TABLE. PLEASE CLARIFY
  
 10)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 PRODUCT APPROVALS:
 A)PRODUCT APPROVALS ARE REQUIRED FOR CASTCRETE
 LINTELS OR THE FLORIDA STATEWIDE APPROVAL NUMBER ADDED
 TO THE LINTEL SCHEDULE
 B)PRODUCT APPROVALS ARE REQUIRED FOR SIMPSON/USP
 CONNECTOR OR THE STATEWIDE APPROVAL NUMBERS MAY BE
 ADDED TO THE CONNECTOR SCHEDULE
 C)PROVIDE THE TYPE OF ASSEMBLY FROM THE GAF RUBEROID
 PRODUCT APPROVAL THAT WILL BE USED ON THE ROOF. PLEASE
 NOTE THAT IN 140 MPH EXP B THE ZONE 3 AREA OF THE ROOF
 HAS A PSF VALUE OF -89.0, MOST ASSEMBLIES MAX OUT AT
 -75 PSF WITH A LIMITATION #7 (SEE PAGE32) THAT REQUIRES
 CALCULATIONS TO ENHANCE THE FASTENERS TO MEET THE ZONE
 3 REQUIREMENTS. HAVE DESIGNER OF RECORD PROVIDE THESE
 CALC'S.
 D)POMA STORM PANEL NOA HAS EXPIRED, NEW NOA NUMBER IS
 NOW POSTED ON MIAMI-DADE SITE BUT NOT UNDER POMA
  
 11)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. MAKE CORRECTIONS FOR FLAT ROOF TYPE
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  