2007-06-04 16:35:53 | BUILDING PLAN REVIEW |
| PERMIT: 07040698 |
| ADD: 6118 WILDCAT RUN |
| CONT: WILLIAM BELL CONSTRUCTION |
| TEL: (561)741-8655 |
| |
| |
| FL BLD CODE= 2004 FLORIDA RESIDENTIAL CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| SUBMITTED ARE MANUFACTURERERS SPECS FOR MAJESTIC BR/BC |
| WOODBURNING FIREPLACES |
| |
| HIGHLIGHTED ON SHEET 20 UNDER CAUTION:IT STATES IF |
| YOU USE AN UNAPPROVED COMPONENT TO MAKE ANY |
| MODIFICATIONS, YOU MAY CREATE A POSSIBLE FIRE HAZARD |
| AND WILL VOID THE CFM CORPORATION WARRANTY. |
| RESIDENTIAL CODE 1002.1 FACTORY-BUILT CHIMNEYS SHALL BE |
| LISTED AND LABELED AND SHALL BE |
| INSTALLED AND TERMINATED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| |
| R1002.2 DECORATIVE SHROUD. DECORATIVE SHROUDS SHALL NOT |
| BE INSTALLED AT THE TERMINATION OF A FACTORY-BUILT |
| CHIMNEYS EXCEPT WHERE SHROUDS ARE LISTED AND LABELED |
| FOR USE WITH THE SPECIFICFACTORY-BUILT CHIMNEY |
| SYSTEMAND INSTALLED IN ACCORDANCE WITH THE MANUFACTER'S |
| INSTALLATIONINSTRUCTIONS. |
| |
| RESIDENTIAL CODE 1002.1 FACTORY-BUILT CHIMNEYS SHALL BE |
| LISTED AND LABELED AND SHALL BE INSTALLED AND |
| TERMINATED IN ACCORDANCE WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. |
| PLEASE PROVIDE THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS IT APPEARS IN THIS DRAWING THESPARK |
| ARESTOR IS MISSING. |
| |
| DESIGN#1 FROM ARCHITECT STEPHENYECKES; WRITTEN |
| NOTIRIZED PERMISSION WILL NEED TO BE SOUGHT FROM THE |
| MANUFACTURERER FOR THE PROPOSED DECORATIVE WEATHER |
| HEAD. IN SPEAKING WITH THE DESIGN PROFESSIONAL IT WAS |
| STATED WRITTEN APPROVAL MUST BE OBTAINED, AND NO |
| COMBUSTIBLE MATERIAL WOULD BE ALLOWED ABOVE THE PAN |
| FLASHING AND STORM COLLAR. IN THE PRESENT DESIN PLANS |
| STILL INDICATE THE USE OF FOAM TRIM AND THE DECKING FOR |
| THE WALLS AND ROOF SHEATHING AREN'T IDENTIFIED. PLANS |
| ALSO NOW INDICATE THE FRAMING TO BE METAL STUDS BUT NO |
| CONSIDERATION HAS BEEN GIVEN TO BRACING NOR THE BOTTOM |
| ANCHOR HAS BEEN IDENTIFIED. |
| |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |