Date |
Text |
2007-04-26 16:45:47 | BUILDING PLAN REVIEW |
| PERMIT: 07040698 |
| ADD: 6118 WILDCAT RUN |
| CONT: WILLIAM BELL CONSTRUCTION |
| TEL: (561)741-8655 |
| |
| |
| FL BLD CODE= 2004 FLORIDA RESIDENTIAL CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| SUBMITTED ARE TWO DESIGNS: |
| |
| DESIGN # 1: |
| RESIDENTIAL CODE 1002.1 FACTORY-BUILT CHIMNEYS SHALL BE |
| LISTED AND LABELED AND SHALL BE |
| INSTALLED AND TERMINATED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| |
| R1002.2 DECORATIVE SHROUD. DECORATIVE SHROUDS SHALL NOT |
| BE INSTALLED AT THE TERMINATION OF A |
| FACTORY-BUILT CHIMNEYS EXCEPT WHERE SHROUDS ARE LISTED |
| AND LABELED FOR USE WITH THE SPECIFICFACTORY-BUILT |
| CHIMNEY SYSTEMAND INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTER'S INSTALLATIONINSTRUCTIONS. |
| |
| |
| DESIGN# 2; |
| RESIDENTIAL CODE 1002.1 FACTORY-BUILT CHIMNEYS SHALL BE |
| LISTED AND LABELED AND SHALL BE |
| INSTALLED AND TERMINATED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| PLEASE PROVIDE THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS IT APPEARS IN THIS DRAWING THE |
| SPARK ARESTOR IS MISSING. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |