Plan Review Notes
Plan Review Notes For Permit 07040689
Permit Number 07040689
Review Stop E
Sequence Number 3
Notes
Date Text
2007-08-23 18:02:20 
 *** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE SUBSTANTIAL NEW COMMENTS. THIS
 IS THE FIRST REVIEW OF MANY ITEMS WHICH ARE NOW ON
 PLANS WHICH WERE NOT ON PLANS PREVIOUSLY SUBMITTED.
 PLEASE SEE THIS IS THE FIRST TIME THAT A PANEL
 SCHEDULE, LOAD CALCULATIONS AND RISER HAVE BEEN
 SUBMITTED FOR REVIEW CREATING SEVERAL NEW COMMENTS.
  
 1) NOTE: PLEASE SEE THE NEW PANEL WHICH SEEMS TO BE
 REPLACING THE EXISTING PANEL DOES NOT CORRELATE WITH
 RISER OR LOAD CALCULATIONS.
 PLEASE SEE MANY OF THE FOLLOWING ITEMS WHICH ARE NOT
 CODE COMPLIANT.
 A) PLEASE SEE THE RISER SHOWS THIS AS AN EXISTING
 3-PHASE PANEL AND FEEDERS YET THE NEW PANEL IS SHOWN AS
 A 1-PHASE PANEL?
 B) PLEASE SEE NO OVER CURRENT PROTECTION IN THE
 EXISTING MAIN IS BEING SHOWN ON THE RISER FOR NEW
 PANEL. THIS WAS REQUESTED ON THE TWO PREVIOUS REVIEWS
 AND THE INFORMATION SUBMITTED IS NOT COMPLETE. ONLY
 SHOWS 2/0 FOR FEEDERS AND BEING 3-PHASE YET AGAIN NEW
 PANEL IS 1-PHASE.
 C) PLEASE SEE THE VOLTAGE OF THE PANEL IS BEING SHOWN
 AS 120/240 YET THE LOAD CALCULATIONS INDICATES THIS
 SERVICE AND CALCULATIONS AS 120/208V?
 D) PLEASE SEE THERE A NUMEROUS BREAKERS ON THE PANEL
 SCHEDULE WHICH ARE SHOWN AS 2-POLE BREAKERS FEEDING
 SINGLE POLE CIRCUITS WHICH CAN NOT BE POSSIBLE. PLEASE
 SEE THERE ARE 2-POLE CIRCUITS SHOWN FOR THREE POLE
 SPACES. PLEASE SEE THERE ARE THREE POLE SPACES WITH TWO
 POLES CIRCUIT BREAKERS.
 *** NONE OF THESE THINGS CORRELATE AND IT IS NOT
 POSSIBLE. PLEASE CORRELATE ALL BREAKERS AND CIRCUITS.
 PLEASE BE SURE TO CORRECTLY INDICATE IF THESE ARE
 1-POLE, 2-POLEPR 3-POLE DEPENDING ON THE CIRCUIT AND
 WHETHER OR NOT PANEL IS SINGLE PHASE OR THREE PHASE.
 PLEASE BE SURE ALL SPACES IN PANEL CORRELATE WITH THE
 PHASES AND SPACE EACH BREAKER WILL TAKE.
 408.4.
 E) PLEASE SEE RISER INDICATES PANEL AS 150AMP YET PANEL
 IS BEING SHOWN AS 225AMP. IS THE EXISTING 150AMP AND
 THE NEW ONE WILL BE 225AMP?
 F) PLEASE SEE 110.14 AND 310.16 AS 2/0 CONDUCTORS ARE
 NOT RATED FOR 200 OR 225AMP OCP. PLEASE KNOW YOU MAY
 ONLY USE THE 75 DEGREE COLUMN IN THE NEC UNLESS LUGS
 ARE 90 DEGREE RATED. (MOST EQUIPMENT IS 75, SPECIAL
 ORDER FOR 90 ONLY)
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS WHICH MEET THE
 MINIMUM AS REQUIRED PER THE NEC 220.
 PLEASE SEE THE LOADS SHOWN FOR THE A/C EXCEED THE
 BRANCH CIRCUIT RATING OF THE BREAKERS AND
 CONDUCTORS.240.4, 310.16 ( THIS IS BASED ON THESE BEING
 SHOWN IN A SINGLE PHASE PANEL. THIS MAY BE OK, IF
 INDEED THIS IS A THREE PHASE PANEL AND SERVICE.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125% AS REQUIRED
 PER 215.3, 230.42 ETC. (LIGHTING).
 PLEASE SEE 422.13 AS THE MINIMUM LOAD FOR WATER HEATERS
 ARE REQUIRED TO BE FIGURED AND SHOWN AT 125%.
 PLEASE SEE 220.87
  
 3) NOTE: PLEASE SEE NOW THAT PANEL HAS MOVED WHICH IT
 WAS SHOWN ON PREVIOUS PLANS IN CLOSET, THE PLANS ARE
 NOW MISSING THE REQUIRED WATER HEATER DISCONNECT PER
 422.31.
  
 4) NOTE: GFI REQUIRED FOR BATH ROOM RECEPTACLES
 210.8B1
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]