Plan Review Notes
Plan Review Notes For Permit 07040689
Permit Number 07040689
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-11 16:16:15 
  
 **** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED
 ON PLANS AND INFORMATION SHOWN.
  
 1) NOTE: PLEASE SEE TITLE BLOCKS ARE MISSING THE FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FAC 61G1-16.002, FS 481.219.
  
 2) NOTE:PLEASE SEE NOT ALL CIRCUITING IS SHOWN ON
 PLANS AS PREVIOUSLY REQUESTED. PLEASE SEE THERE NOW AN
 INDICATION OF A NEW PANEL WITH NUMEROUS CIRCUITS WHICH
 ARE NOT ON PLANS?
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4, 240.4, 310.16
  
 3) NOTE: PLEASE SEE NO CONTROLS FOR LIGHTING WAS
 SUBMITTED WITH COMPLIANCE TO THE FBC CHAPTER 13 AS
 PREVIOUSLY GIVEN.
 REVIEW OF THESE CAN NOT BE DONE AT THIS TIME AS NONE
 ARE SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.2
 PLEASE INDICATE DEVICES, TYPES FOR COVERAGE, MAXIMUM
 TIMES ON DEVICES ETC.
  
 4) NOTE: PLEASE SEE THE LOCATION OF THE PANEL AS SHOWN
 IS NOT PERMITTED. 408.7, 110.26, 240.24 ETC.
  
 5) NOTE: PLEASE SEE NO INFORMATION FOR THIS NEW PANEL
 WAS SHOWN ON HOW AND WHERE THIS PANEL IS FED.
 PLEASE SEE NO RISER DIAGRAM, WIRING, CONDUCTORS ETC ON
 WHERE THIS NEW PANEL IS FED.
 PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED
 INDICATING ANY NEW LOADS FOR THIS PANEL WHICH IS BEING
 ADDED TO THE EXISTING ELECTRICAL SERVICE?
 PLEASE SEE 215.5, 220, 240, 310.16, 240.4 ETC.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved