Date Text
2007-04-27 09:24:18** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE MISSING CIRCUITING FOR NEW
 ELECTRICAL WHICH IS TO BE SHOWN. PLEASE CORRELATE WITH
 A PANEL SCHEDULE TO BE SUBMITTED.
 PLEASE INCLUDE CONDUCTOR SIZES ALONG WITH OVER CURRENT
 PROTECTION DEVICES.
 FBC 106.3.5.1.2
 408.4, 310.16, 240.4
  
 2) NOTE: PLEASE SEE THE LOCATION OF THE NEW ELECTRICAL
 PANEL DOES NOT MEET 110.26, 408.7, 240.24 OF THE NEC
 FOR MINIMUM CLEARANCES, VICINITY OF EASILY IGNITABLE
 MATERIALS ETC.
 PLEASE RELOCATE.
  
 3) NOTE: PLEASE KNOW DEPENDING ON THE LOCATION OF THE
 NEW PANEL, A DISCONNECT MAY BE REQUIRED FOR THE WATER
 HEATER.
 422.31
  
 4) NOTE: PLEASE PROVIDE LIGHTING ON PLANS AND
 CONTROLS.
 PLEASE SEE LS 101 7.8, AND 7.9 AS AN EMERGENCY BATTERY
 BACK UP LIGHT OF SOME KIND WILL BE REQUIRED.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2,OF THE
 2004 FBC W/2006 REVISIONS.
  
  
 6) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]