Plan Review Notes
Plan Review Notes For Permit 07040663
Permit Number 07040663
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-26 12:15:02 
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE FEEDER CONDUIT AND CONDUCTOR SIZES,TYPES
 AND OCP. INDICATE THE LOCATION OF THE HOUE PANEL AND
 FEEDER ROUTE ON THE SITE PLAN.
  
 2} PROVIDE A CALCULATION FOR THE FOR THE LOAD(S)
 SERVED. SEE ARTICLE 555.12 NEC.
  
 3} A DISCONNECTING MEANS PER 225.31 SHALL BE LOCATED
 PER 555.7.PLEASE INDICATE INTENDED LOCATION ON THE
 PLAN.
  
 4} PLEASE PROVIDE SPECIFICATIONS FOR THE SHORE POWER
 RECEPTACLE EQUIPMENT TO BE INSTALLED ON THE DOCK.
  
 5} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 6} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED. INCREASE THE VALUE AT THE
 COUNTER WHEN RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  