Plan Review Notes
Plan Review Notes For Permit 07040638
Permit Number 07040638
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-20 11:43:05*** DENIED ***
 1) NO INFORMATION GIVEN ON HOOD TO DO PROPER REVIEW
 (IE. IF USED OR NEW,IF UL APPROVED, TYPE OF HOOD,
 MATERIALS MADE OF, SIZE OF HOOD ETC.), PLEASE CORRECT.
  
 2) PLEASE SHOW WHAT MATERIAL THE 12" SUPPLY AIR DUCT IS
 MADE OF, SEE 2004 FBC/M 506.3.1.2.
  
 3) PLEASE SHOW HOW EXHAUST AND SUPPLY FANS ARE TO BE
 SECURED TO THE CURBS TO WITH STAND 140 MPH WINDS AND
 COMPLY WITH 2004 FBC 1609.
  
 4) SEE PLANS PAGE 1, SECTION, PLEASE SHOW WHAT SIZE
 UNISTRUT IS TO BE USED.
  
 5) PLEASE NOTE ON PLANS SF1 CURB TO BE SECURED SAME AS
 EF1, IF NOT THEN SHOW DETAIL.
  
 6) PLEASE SHOW ON PLANS THAT A GUARD WILL BE INSTALLED
 ON ROOF TOP NEAR EDGE OF WALL, SEE 2004 FBC/M 304.10.
  
 *** 2004 FBC/M 304.10 GUARDS.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL EXTEND NOT LESS
 THAN 30 INCHES (762 MM) BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT AND THE TOP OF
 THE GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES
 (1067 MM) ABOVE THE ELEVATED SURFACE ADJACENT TO THE
 GUARD. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE AND
 SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING .
  
 7) PLEASE SUBMIT TWO SETS OF PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.