Plan Review Notes
Plan Review Notes For Permit 07040621
Permit Number 07040621
Review Stop B
Sequence Number 9
Notes
Date Text
2008-06-30 10:53:06BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 SHEET GV-102 THE REVISION INDICATES THE REMOVAL OF
 RATED SMOKE PARTITIONS FOR THE INCIDENTIAL MECHANICAL
 CHASE AND ELECTRICAL ROOM ON THE SECOND FLOOR LEVEL.
 INCIDENTIAL USE AREAS AS PER TABLE
 302.1.1.1REQUIRES A 1 HOUR SEPERATION WITH THE
 EXCEPTION FOR FULLY SPRINKLED BUILDINGS WHICH THIS HAS.
 IN 302.1.1.1 WHERE TABLE 302.1.1 PERMITS AN AUTOMATIC
 FIRE -EXTINGUISHING SYSTEM WITHOUT A FIRE-BARRIER, THE
 INCIDENTIAL USE AREA SHALL BE SEPERATED BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.