Plan Review Notes
Plan Review Notes For Permit 07040621
Permit Number 07040621
Review Stop E
Sequence Number 8
Notes
Date Text
2008-02-15 08:52:092008-02-15 08:52:09
  
 *** DENIEDREVISIONS***
  
 1) NOTE: PLEASE SEE AS REQUESTED ON ALL PREVIOUS
 REVIEWS. PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS FOR
 EGRESS PATHS FOR STAIRS UNDER NORMAL AND EMERGENCY
 CONDITIONS PER LS 1017.8.1.3 AND 7.9.2.2.
 THE ONLY SUBMITTED LEVELS ARE THE LEVELS UNDER
 EMERGENCY WHICH ARE OK, HOWEVER NO LEVELS UNDER NORMAL.
 THE NORMAL LIGHTING LEVELS FOR STAIRS IS TEN FOLD WHAT
 IS REQUIRED AS A MINIMUM UNDER EMERGENCY.
 ONCE AGAIN, PLEASE SEE 7.8.1.3 WHICH REQUIRES * 10FT
 CANDLES MINIMUM. THE FOLLOWING IS TEXT WHICH HAS BEEN
 CUT AND PASTED DIRECTLY FROM NFPA-101 2003.
 ***
 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN
 AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
 EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE
 ILLUMINATED AS FOLLOWS:
 (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX
 (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES.
  
 PLEASE SUBMIT
  
 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 OR EXIT LIGHTS. THERE ARE EXCEPTIONS HOWEVER BASED ON
 THE LIGHTING AND CIRCUITING ON PLANS THE EXIT LIGHTS IN
 MAIN ENTRANCE AREA NEED TO BE CIRCUITED AHEAD OF ANY
 SWITCHING OR CONTROL DEVICES AND TO LOCAL BRANCH
 CIRCUIT.
 PLEASE THERE IS THE OCTAGONAL NOTE #1 ON THE NHP-8
 CIRCUIT IN MAIN LOBBY, HOWEVER OCTAGONAL NOTE #1 SHOWS
 THIS AS *NOT USED*.
 PLEASE COORDINATE.
  
  
 PLEASE SUBMIT THE ABOVE. SHEETS EE-001, EP-101, EP-102
 AND EC-102 APPEAR TO BE OK AT THIS TIME. THE OTHER
 SHEETS SUCH AS RISER SHEET WHICH SHOWS LOADS AND PANEL
 SCHEDULES WILL BE GETTING REVISED BASED ON NOTES
 ABOVE.
 REDLINED NEC 517.1 AS THIS APPLIES TO OCCUPANCY AND
 SCOPE OF WORK.
 ONLY SHEETS NOTED AS EE-001, EP-101, EP-102 AND EC-102
 ARE BEING STAMPED. ONE COPY OF THESE SHEETS ARE REMOVED
 FROM ONE SET AND KEPT FOR FILE SET OF PLANS. ONE SET OF
 SHEETS ARE GIVEN BACK FOR THE CONTRACTORS ON-SITE SET.
  
 ** IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-14 19:38:482008-02-14 19:38:49
  
 NOTES TO FOLLOW ONCE COMPLETED. SOME SHEETS ARE OK,
 SOME REMAIN WITH COMMENTS.
2008-02-14 19:27:502008-02-14 19:27:50
  
 IN ELEC FOR REVIEW, PLANS CONTAINS REVISIONS FOR FIRE,
 MECH, BLDG ALSO NOT ONLY ELECTRICAL AS INDICATED ON
 COVER SHEET.