Date |
Text |
2008-02-15 08:52:09 | 2008-02-15 08:52:09 |
| |
| *** DENIEDREVISIONS*** |
| |
| 1) NOTE: PLEASE SEE AS REQUESTED ON ALL PREVIOUS |
| REVIEWS. PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS FOR |
| EGRESS PATHS FOR STAIRS UNDER NORMAL AND EMERGENCY |
| CONDITIONS PER LS 1017.8.1.3 AND 7.9.2.2. |
| THE ONLY SUBMITTED LEVELS ARE THE LEVELS UNDER |
| EMERGENCY WHICH ARE OK, HOWEVER NO LEVELS UNDER NORMAL. |
| THE NORMAL LIGHTING LEVELS FOR STAIRS IS TEN FOLD WHAT |
| IS REQUIRED AS A MINIMUM UNDER EMERGENCY. |
| ONCE AGAIN, PLEASE SEE 7.8.1.3 WHICH REQUIRES * 10FT |
| CANDLES MINIMUM. THE FOLLOWING IS TEXT WHICH HAS BEEN |
| CUT AND PASTED DIRECTLY FROM NFPA-101 2003. |
| *** |
| 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN |
| AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND |
| EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE |
| ILLUMINATED AS FOLLOWS: |
| (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM |
| ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX |
| (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. |
| |
| PLEASE SUBMIT |
| |
| 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| OR EXIT LIGHTS. THERE ARE EXCEPTIONS HOWEVER BASED ON |
| THE LIGHTING AND CIRCUITING ON PLANS THE EXIT LIGHTS IN |
| MAIN ENTRANCE AREA NEED TO BE CIRCUITED AHEAD OF ANY |
| SWITCHING OR CONTROL DEVICES AND TO LOCAL BRANCH |
| CIRCUIT. |
| PLEASE THERE IS THE OCTAGONAL NOTE #1 ON THE NHP-8 |
| CIRCUIT IN MAIN LOBBY, HOWEVER OCTAGONAL NOTE #1 SHOWS |
| THIS AS *NOT USED*. |
| PLEASE COORDINATE. |
| |
| |
| PLEASE SUBMIT THE ABOVE. SHEETS EE-001, EP-101, EP-102 |
| AND EC-102 APPEAR TO BE OK AT THIS TIME. THE OTHER |
| SHEETS SUCH AS RISER SHEET WHICH SHOWS LOADS AND PANEL |
| SCHEDULES WILL BE GETTING REVISED BASED ON NOTES |
| ABOVE. |
| REDLINED NEC 517.1 AS THIS APPLIES TO OCCUPANCY AND |
| SCOPE OF WORK. |
| ONLY SHEETS NOTED AS EE-001, EP-101, EP-102 AND EC-102 |
| ARE BEING STAMPED. ONE COPY OF THESE SHEETS ARE REMOVED |
| FROM ONE SET AND KEPT FOR FILE SET OF PLANS. ONE SET OF |
| SHEETS ARE GIVEN BACK FOR THE CONTRACTORS ON-SITE SET. |
| |
| ** IF THERE ARE QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2008-02-14 19:38:48 | 2008-02-14 19:38:49 |
| |
| NOTES TO FOLLOW ONCE COMPLETED. SOME SHEETS ARE OK, |
| SOME REMAIN WITH COMMENTS. |
2008-02-14 19:27:50 | 2008-02-14 19:27:50 |
| |
| IN ELEC FOR REVIEW, PLANS CONTAINS REVISIONS FOR FIRE, |
| MECH, BLDG ALSO NOT ONLY ELECTRICAL AS INDICATED ON |
| COVER SHEET. |