Plan Review Notes
Plan Review Notes For Permit 07040621
Permit Number 07040621
Review Stop E
Sequence Number 5
Notes
Date Text
2008-01-07 16:26:15*** TEMP FAILED STATUS***
  
 1) NOTE: 2ND SET OF PLANS MISSING SHEET EP101 AND
 EP102. CALLED ARCHITECT AND WILL FED-EX NEW SHEETS TO
 OFFICE.
  
  
  
 ** THE FOLLOWING WILL BE ATTACHED AS PROVISO.
  
 1) NOTE: PLEASE SEE THE LIGHTING LEVELS IN STAIRS WILL
 BE REQUIRED TO SHOW 10FT CANDLES UNDER NORMAL FOR A
 MINIMUM AND IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE SEE 7.8.1.3, 7.9.2.2.
 PLANS SHOWS LEVELS ABOVE 10FT CANDLES FOR BOTH. THIS
 INCLUDES A NEW UPS/IPS SYSTEM WHICH IS NOT REQUIRED.
 ENGINEERS MENTIONED SYSTEM WILL BE REMOVED.
  
 2) NOTE: PLEASE SEE THE CIRCUITING FOR REAR STAIRS AND
 NOTES FOR LIGHTING AS NOTED FOR NHP-6 AND NHP-8 WILL BE
 REQUIRED TO BE UPDATED.
  
 3) NOTE: MAXIMUM TIMES NOT SHOWN ON SYMBOL LEGEND FOR
 OC DEVICE.
 MAXIMUM TIME TO BE 30MINS PER 13-415.1.ABC.1.1.
  
 4) NOTE: MISSING OC DEVICE IN ROOM 159, RED-LINED PER
 13-415.1.ABC.1.1 AND .1.2.
  
 IF THERE ARE ANY QUESTIONS, PLEASE ONCE AGAIN CONTACT
 THIS OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717