Plan Review Notes For Permit 07040621 |
Permit Number |
07040621 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2008-01-07 16:26:15 | *** TEMP FAILED STATUS*** | | | | 1) NOTE: 2ND SET OF PLANS MISSING SHEET EP101 AND | | EP102. CALLED ARCHITECT AND WILL FED-EX NEW SHEETS TO | | OFFICE. | | | | | | | | ** THE FOLLOWING WILL BE ATTACHED AS PROVISO. | | | | 1) NOTE: PLEASE SEE THE LIGHTING LEVELS IN STAIRS WILL | | BE REQUIRED TO SHOW 10FT CANDLES UNDER NORMAL FOR A | | MINIMUM AND IS PERMITTED DOWN TO 1FT CANDLE UNDER | | EMERGENCY. | | PLEASE SEE 7.8.1.3, 7.9.2.2. | | PLANS SHOWS LEVELS ABOVE 10FT CANDLES FOR BOTH. THIS | | INCLUDES A NEW UPS/IPS SYSTEM WHICH IS NOT REQUIRED. | | ENGINEERS MENTIONED SYSTEM WILL BE REMOVED. | | | | 2) NOTE: PLEASE SEE THE CIRCUITING FOR REAR STAIRS AND | | NOTES FOR LIGHTING AS NOTED FOR NHP-6 AND NHP-8 WILL BE | | REQUIRED TO BE UPDATED. | | | | 3) NOTE: MAXIMUM TIMES NOT SHOWN ON SYMBOL LEGEND FOR | | OC DEVICE. | | MAXIMUM TIME TO BE 30MINS PER 13-415.1.ABC.1.1. | | | | 4) NOTE: MISSING OC DEVICE IN ROOM 159, RED-LINED PER | | 13-415.1.ABC.1.1 AND .1.2. | | | | IF THERE ARE ANY QUESTIONS, PLEASE ONCE AGAIN CONTACT | | THIS OFFICE/REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|