2007-12-23 11:37:35 | 2007-12-23 11:37:35 |
| ** DENIED4TH ** |
| |
| ** PLANS CONTAIN SOME ITEMS WHICH MAY BE REDLINED AND |
| WILL NEED TO BE REVISED BEFORE ROUGH HOWEVER PLEASE SEE |
| SOME ITEMS BELOW WHICH MUST BE DONE AT THIS TIME. THE |
| NOTES WITH ** MUST BE ADDRESSED AT THIS TIME. THE NOTES |
| WITHOUT ** WILL STILL NEED TO BE ADDRESSED, HOWEVER MAY |
| BE DONE AT THIS TIME OR BEFORE ROUGH. |
| |
| |
| ** 1) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS |
| LIGHTING PERFORMANCE DONE UNDER TABLE *B* FOR SPACE BY |
| SPACE HOWEVER THERE ARE ALSO SHEETS FOR FORM 400C? |
| PLEASE KNOW THAT IN EITHER CASE, THE SEPARATE LIGHTING |
| PERFORMANCE CALCULATIONS SUBMITTED EACH MUST CONTAIN A |
| COMPLETED TITLE BLOCK FROM THE DESIGN FIRM/ENGINEER OF |
| RECORD ALONG WITH EACH SHEET SIGNED, DATED AND SEALED. |
| PLEASE SEE FAC 61G15-23.002, FS 471.023. |
| PLEASE KNOW THESE MAY BE SENT AND PLACED WITH PLANS AS |
| THE CALCULATIONS ARE OK. |
| AS NEW FORM 400C IS NOW BEING SUBMITTED FOR THE FIRST |
| TIME, MECHANICAL REVIEW WILL BE REQUIRED EVEN AS THIS |
| WAS PREVIOUSLY PASSED. |
| |
| 2) NOTE: PLEASE CLARIFY WHERE THE MAXIMUM TIMES ON |
| OCCUPANCY SENSORS ARE? |
| PLEASE CLARIFY TYPE OF OCCUPANCY DEVICE. IR? ETC |
| 13-415.1.ABC.1.1, .1.2 |
| PLEASE SEE MISSING DEVICE FROM ROOM 159. |
| |
| ** 3) NOTE: PLEASE CLARIFY THE NEW UPS WHICH HAS NOW |
| BEEN ADDED TO PLANS WHICH WAS NOT ON PREVIOUS PLANS. |
| THE RESPONSE LETTER MENTIONS THE FIXTURES WOULD NOT |
| PROVIDE THE OUTPUT FOR MINIMUM LIGHTING LEVELS, HOWEVER |
| AS MENTIONED ON ALL PREVIOUS REVIEWS THE LIGHTING |
| LEVELS UNDER NORMAL FOR STAIRS IS 10FT CANDLES PER |
| 7.8.1.3 AND IS PERMITTED TO GO DOWN TO 1FT CANDLE UNDER |
| EMERGENCY CONDITIONS PER 7.9.2.2. THE AVERAGE FT CANDLE |
| LEVELS UNDER EMERGENCY ARE NOT SHOWN HOWEVER BASED ON |
| THE NUMBER OF POINTS AND THE LEVELS SHOWN IT SEEMS |
| PERHAPS PREVIOUS NOTES WERE NOT TYPED IN A MANOR WHICH |
| WAS UNDERSTOOD. |
| PLEASE CLARIFY RESPONSE AND LIGHTING LEVELS BEING |
| SHOWN. PLEASE SEE THE |
| REAR STAIR ON PLANS CONTAIN A NOTE WHICH MENTIONS TO |
| PLACE ON LOBBY 100 NHP-6 CIRCUIT YET THIS SAME REAR |
| STAIR HAS A NOTE TO CIRCUIT LIGHTS TO NHP-8. HOW WILL |
| THIS WORK AS THIS PLACES 220/240V ON FIXTURES. THIS |
| MUST BE A MISPRINT. |
| PLEASE SEE THE PANEL SCHEDULE DOES NOT INDICATE ANY |
| CIRCUITING TO THE UPS AND SHOWS CIRCUITS TO FIXTURE |
| UNITS. |
| PLEASE CALL TO GO OVER THIS FOR LIGHTING. |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-12-23 11:37:07 | 2007-12-23 09:57:07 |
| REVIEW COMMENCED. |
2007-12-22 17:04:41 | 2007-12-22 17:04:41 |
| |
| IN ELECTRICAL FOR REVIEW. |