Date |
Text |
2007-10-29 15:25:04 | |
| ** DENIED 3RD REVIEW ** |
| |
| ** PLEASE SEE NOTES FROM PREVIOUS TWO REVIEWS WHICH |
| STILL NEED TO BE ADDRESSED. |
| PLEASE SEE AS STATED ON PREVIOUS REVIEWS, REVIEW NOTES |
| CAN ONLY BE GIVEN ON PLANS AND DOCUMENTATION SUBMITTED. |
| AS NOTED THERE MAY ALSO BE NEW NOTES FOR ITEMS WHICH |
| COULD NOT BE REVIEWED PREVIOUSLY. |
| |
| 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, PLEASE |
| INDICATE AREAS WHICH WIRING METHODS FOR NEC 517 WILL BE |
| REQUIRED. PLEASE SEE THE RESPONSE IN LETTER AND MEETING |
| HELD BEFORE PLANS WERE SUBMITTED WAS THAT THE BUILDING |
| WAS ONLY GOING TO BE BUSINESS AND ADMINISTRATIVE |
| OFFICES. |
| PLEASE KNOW THAT IT HAS COME TO OUR ATTENTION AND PER |
| PLANS SUBMITTED THERE WILL BE ROOMS IN WHICH DOCTORS |
| WILL BE DOING EXAMS ALONG WITH EQUIPMENT. THE OCCUPANCY |
| DOES NEED TO BE DESIGNATED AS A HEALTH CARE FACILITY IN |
| ORDER FOR WIRING METHODS IN 517 TO BE REQUIRED IN SOME |
| ROOMS. PLEASE SEE AREAS SUCH AS THE DOCTOR'S ADMIN |
| OFFICES, RECEPTION, HALLWAYS, ETC ARE NOT AREAS WHICH |
| FALL UNDER 517, HOWEVER EXAM ROOMS AND THE LIKE ARE. |
| PLEASE ADJUST NOTES AND WIRING METHODS PER 517. PLEASE |
| SEE 517.1, 517.10 AND 517.13. |
| PLEASE SEE THE FOLLOWING WHICH IS TAKEN DIRECTLY FROM |
| THE NEC COMMENTARY. |
| |
| *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY |
| TO ALL TYPES OF HEALTH CARE FACILITIES. THE |
| REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE |
| NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC |
| MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES |
| WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE |
| WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE |
| REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER |
| PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS |
| ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE |
| REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45 |
| IN ARTICLE 517.* |
| |
| THIS IS ONLY ONE PART OF THE NEC PROVIDED. PLEASE KNOW |
| THAT ANY WORK DONE UNDER SHELL/ADDITION PHASE II PERMIT |
| MAY BE AFFECTED. |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13 (ALL). PLEASE SEE |
| THAT THE TWO PREVIOUS REVIEWS MENTIONED THERE WERE |
| SEVERAL SECTIONS OF THIS CHAPTER WHICH NEEDED TO BE |
| ADDRESSED AS DESIGN FOR CHAPTER 13 LIGHTING CONTROLS |
| HAD NOT BEEN SHOWN. |
| PLEASE SEE THERE ARE STILL ITEMS FOR SEVERAL LOCATIONS |
| WHICH HAVE NOT HAD THE COMMENTS ADDRESSED. |
| |
| A) PLEASE SEE THERE ARE SEVERAL SEPARATE SPACES WHERE |
| NO LIGHTING CONTROLS FOR OVER RIDES ARE SHOWN. PLEASE |
| SEE PREVIOUS TWO REVIEWS SECTION 13-415.1.ABC.1.2. |
| PLEASE SEE FOR EXAMPLE SOME OF THESE LOCATIONS ARE THE |
| SAME IN WHICH WAS REDLINED ON PREVIOUS PLANS. PLEASE |
| SEE 123, 183, 161, 162, 159, 131, 110, 112, 209, 208 |
| ETC. THESE ARE NOTED FOR SOME OF THESE LOCATIONS WHICH |
| CONTAIN THE FLOOR TO CEILING HEIGHT PARTITIONS AS |
| STATED IN THE CODE; HOWEVER NO OVER RIDE DEVICES ARE |
| SHOWN. |
| |
| B) PLEASE SEE AREAS IN WHICH THE OCCUPANT MUST SEE THE |
| LIGHTING IN WHICH IS BEING OVER RIDDEN OR CONTROLLED. |
| PLEASE SEE THERE IS AN EXCEPTION HOWEVER NO DETAILS FOR |
| THE EXCEPTION FOR INDICATOR/PILOT LIGHTS ARE SHOWN. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2. PLEASE SEE FOR |
| EXAMPLE THE FIRST FLOOR FOR CIRCUITS 60, 30 AND 32 |
| WHICH ARE LV SWITCHES SHOWN AS THE LOBBY AREA HOWEVER |
| FROM THIS LOCATION THE OCCUPANT CAN NOT SEE THE |
| LIGHTING THEY ARE CONTROLLING. |
| PLEASE SEE TENANT SPACES ALSO FOR EXAMPLE AS THE COMMON |
| AREA LIGHTING DOES NOT INDICATE ANY OVER RIDE |
| CONTROL(S). THE OCCUPANT ENTERING INTO THE SPACE/AREA |
| NEEDS TO HAVE AN OVER RIDE OF THE TIMED SCHEDULED |
| SYSTEM. |
| PLEASE SEE FOR EXAMPLE THE OCTAGONAL NOTE #4 ON SHEET |
| EL-101 AS THIS MENTIONS CIRCUIT NHP-11 YET THIS CIRCUIT |
| ON PANEL SCHEDULE IS FOR THE 2ND FLOOR AND FOR A |
| RECEPTACLE CIRCUIT AND NOTED FOR SHELL. HOW IS THIS |
| POSSIBLE? |
| PLEASE ALSO SEE FOR EXAMPLE THE LIGHTING WHICH IS SHOWN |
| FOR HOUSE FOR SHELL FOR SECOND FLOOR WHICH DOES NOT |
| SHOW ANY OVER RIDE DEVICES. |
| PLEASE ALSO SEE FOR EXAMPLE THE LOBBY AREA WHICH IS |
| BEING ILLUMINATED BY LIGHTING IN THE CEILING FROM THE |
| 2ND FLOOR LIGHTING CONTROL PANEL. WHERE ARE THE OVER |
| RIDE DEVICES FOR THE FRONT ENTRANCE AREA? THIS IS AN |
| OPEN AREA FOR THE FIRST FLOOR. |
| PLEASE CLARIFY CIRCUITING FOR FOUNDATION ROOM, |
| CONFERENCE ROOM ON SECOND FLOOR AS THESE ARE SHOWN TO |
| CIRCUIT 42 AND ALSO A 42A AND 42B? THIS IS UNCLEAR HOW |
| THESE ARE CIRCUITED AS PANEL SCHEDULE IS BEING ASSUMED |
| TO BE NHP2. THIS PANEL SCHEDULE ONLY INDICATES ONE #42 |
| CIRCUIT. *LIGHTING*. |
| THE FLOORS ARE REQUIRED TO BE SEPARATED. |
| THESE ARE SOME EXAMPLES, AND IN NO WAY NOTES ALL |
| POSSIBLE SCENERIOS. |
| ** PLEASE SEE THAT THERE ARE SEVERAL AREAS IN WHICH |
| LIGHTING CONTROLS ARE NOT YET COMPLETE FOR CHAPTER 13 |
| AS NOTED. |
| |
| C) PLEASE SEE THE METHOD OF CALCULATIONS SUBMITTED AS |
| *WHOLE BUILDING * METHOD *A* MAY NOT BE USED. THIS IS |
| AN EXISTING BUILDING WHICH IS CURRENTLY BEING REMODELED |
| UNDER METHOD *B*. |
| THIS ALSO FALLS UNDER RENOVATED BUILDINGS PER |
| 13-101.1.3. PLEASE SEE AS STATED ON PREVIOUS REVIEW THE |
| METHOD CALCULATION WOULD DEPEND ON KNOWN FACTORS AND AS |
| THERE ARE STILL PORTIONS OF THIS BUILDING NOT |
| COMPLETED, METHOD *A* COULD NOT BE USED EITHER PER |
| 13-101.6. |
| PLEASE SUBMIT THE CORRECT METHOD WHICH AS STATED IN THE |
| TWO SECTIONS GIVEN COULD BE *B* OR *C*.13-415.1.B.1 |
| PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS SHALL MEET |
| 13-415. |
| ** PLEASE SEE MECHANICAL COMMENTS AS THIS MAY ALSO BE |
| PART OF THEIR REVIEW NOTES. |
| |
| D) PLEASE SUBMIT COMPLETE INFORMATION FOR LIGHTING |
| CONTROL PANELS/SYSTEM BEING PROPOSED. PLEASE SEE THE |
| PLANS ONLY FOR A *LIGHTING CONTROL PANEL* WHICH DOES |
| NOT PROVIDE THE INFORMATION AS NEEDED FOR COMPLIANCE |
| WITH SECTIONS A AND B OF THIS SAME NOTE #2 |
| |
| E) PLEASE PROVIDE NOTE ON PLANS FOR 13-413.1.ABC.2 |
| WHICH CONTAINS SUB SECTIONS 2.1 AND 2.2. |
| THIS WAS RECENTLY CONFIRMED WITH THE FLORIDA BUILDING |
| COMMISSION. |
| |
| 3) NOTE: PLANS NOW INDICATE THE PHOTO-METRICS FOR |
| EGRESS PATHS FOR NORMAL CONDITIONS, HOWEVER COULD NOT |
| LOCATE LEVELS FOR EMERGENCY CONDITIONS. THIS COMMENT IS |
| NOT FOR STAIRS AS THE SAME FIXTURES ARE FOR BOTH |
| CONDITIONS. |
| PLEASE CLARIFY THE EGRESS PATHS FOR CORRIDORS AS THE |
| LEVELS ARE DONE SHOWING GENERAL FIXTURES AS WELL AS |
| EMERGENCY. |
| LS 101 7.8 AND 7.9. |
| FAC 61G15-33.004 |
| |
| 4) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOMS WHICH |
| ARE ON EE-401. PLEASE CLARIFY THE DESIGNATIONS AS ROOM |
| #216 IS BEING NOTED FOR 2ND FLOOR HOWEVER 216 ON THE |
| SECOND FLOOR IS A CORRIDOR. PLEASE SEE THE ROOM FOR THE |
| ELECTRICAL CLOSET IS SHOWN AS 203 ON EL-102. THIS IS A |
| MINOR COMMENT HOWEVER AS PLANS ARE COMING BACK FOR |
| OTHER COMMENTS, PLEASE CORRECT AT THIS TIME. |
| |
| 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO |
| FLORIDA STATUTES 553.80(2)(B). THERE ARE CODES WHICH |
| WERE REPEATED ONCE AGAIN WHICH WERE NOTED THREE TIMES. |
| THERE WILL BE A FEE ASSESSED AS REQUIRED BY THE |
| STATUTES. THE FEE AMOUNT IS DUE BEFORE PLANS MAY BE |
| RESUBMITTED. IT IS RECOMMENDED THAT THE COMMENTS ARE |
| GONE OVER BEFORE PLANS ARE RESUBMITTED. ONE COPY OF THE |
| ELECTRICAL SHEETS IS BEING RETAINED BY THIS OFFICE. |
| |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-10-29 10:17:40 | |
| |
| REVIEW COMMENCED. |
2007-10-27 12:23:51 | 2007-10-27 12:23:51 |
| |
| IN ELEC FOR REVIEW |