Plan Review Notes
Plan Review Notes For Permit 07040621
Permit Number 07040621
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-29 15:25:04 
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS TWO REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
 PLEASE SEE AS STATED ON PREVIOUS REVIEWS, REVIEW NOTES
 CAN ONLY BE GIVEN ON PLANS AND DOCUMENTATION SUBMITTED.
 AS NOTED THERE MAY ALSO BE NEW NOTES FOR ITEMS WHICH
 COULD NOT BE REVIEWED PREVIOUSLY.
  
 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, PLEASE
 INDICATE AREAS WHICH WIRING METHODS FOR NEC 517 WILL BE
 REQUIRED. PLEASE SEE THE RESPONSE IN LETTER AND MEETING
 HELD BEFORE PLANS WERE SUBMITTED WAS THAT THE BUILDING
 WAS ONLY GOING TO BE BUSINESS AND ADMINISTRATIVE
 OFFICES.
 PLEASE KNOW THAT IT HAS COME TO OUR ATTENTION AND PER
 PLANS SUBMITTED THERE WILL BE ROOMS IN WHICH DOCTORS
 WILL BE DOING EXAMS ALONG WITH EQUIPMENT. THE OCCUPANCY
 DOES NEED TO BE DESIGNATED AS A HEALTH CARE FACILITY IN
 ORDER FOR WIRING METHODS IN 517 TO BE REQUIRED IN SOME
 ROOMS. PLEASE SEE AREAS SUCH AS THE DOCTOR'S ADMIN
 OFFICES, RECEPTION, HALLWAYS, ETC ARE NOT AREAS WHICH
 FALL UNDER 517, HOWEVER EXAM ROOMS AND THE LIKE ARE.
 PLEASE ADJUST NOTES AND WIRING METHODS PER 517. PLEASE
 SEE 517.1, 517.10 AND 517.13.
 PLEASE SEE THE FOLLOWING WHICH IS TAKEN DIRECTLY FROM
 THE NEC COMMENTARY.
  
 *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.*
  
 THIS IS ONLY ONE PART OF THE NEC PROVIDED. PLEASE KNOW
 THAT ANY WORK DONE UNDER SHELL/ADDITION PHASE II PERMIT
 MAY BE AFFECTED.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13 (ALL). PLEASE SEE
 THAT THE TWO PREVIOUS REVIEWS MENTIONED THERE WERE
 SEVERAL SECTIONS OF THIS CHAPTER WHICH NEEDED TO BE
 ADDRESSED AS DESIGN FOR CHAPTER 13 LIGHTING CONTROLS
 HAD NOT BEEN SHOWN.
 PLEASE SEE THERE ARE STILL ITEMS FOR SEVERAL LOCATIONS
 WHICH HAVE NOT HAD THE COMMENTS ADDRESSED.
  
 A) PLEASE SEE THERE ARE SEVERAL SEPARATE SPACES WHERE
 NO LIGHTING CONTROLS FOR OVER RIDES ARE SHOWN. PLEASE
 SEE PREVIOUS TWO REVIEWS SECTION 13-415.1.ABC.1.2.
 PLEASE SEE FOR EXAMPLE SOME OF THESE LOCATIONS ARE THE
 SAME IN WHICH WAS REDLINED ON PREVIOUS PLANS. PLEASE
 SEE 123, 183, 161, 162, 159, 131, 110, 112, 209, 208
 ETC. THESE ARE NOTED FOR SOME OF THESE LOCATIONS WHICH
 CONTAIN THE FLOOR TO CEILING HEIGHT PARTITIONS AS
 STATED IN THE CODE; HOWEVER NO OVER RIDE DEVICES ARE
 SHOWN.
  
 B) PLEASE SEE AREAS IN WHICH THE OCCUPANT MUST SEE THE
 LIGHTING IN WHICH IS BEING OVER RIDDEN OR CONTROLLED.
 PLEASE SEE THERE IS AN EXCEPTION HOWEVER NO DETAILS FOR
 THE EXCEPTION FOR INDICATOR/PILOT LIGHTS ARE SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2. PLEASE SEE FOR
 EXAMPLE THE FIRST FLOOR FOR CIRCUITS 60, 30 AND 32
 WHICH ARE LV SWITCHES SHOWN AS THE LOBBY AREA HOWEVER
 FROM THIS LOCATION THE OCCUPANT CAN NOT SEE THE
 LIGHTING THEY ARE CONTROLLING.
 PLEASE SEE TENANT SPACES ALSO FOR EXAMPLE AS THE COMMON
 AREA LIGHTING DOES NOT INDICATE ANY OVER RIDE
 CONTROL(S). THE OCCUPANT ENTERING INTO THE SPACE/AREA
 NEEDS TO HAVE AN OVER RIDE OF THE TIMED SCHEDULED
 SYSTEM.
 PLEASE SEE FOR EXAMPLE THE OCTAGONAL NOTE #4 ON SHEET
 EL-101 AS THIS MENTIONS CIRCUIT NHP-11 YET THIS CIRCUIT
 ON PANEL SCHEDULE IS FOR THE 2ND FLOOR AND FOR A
 RECEPTACLE CIRCUIT AND NOTED FOR SHELL. HOW IS THIS
 POSSIBLE?
 PLEASE ALSO SEE FOR EXAMPLE THE LIGHTING WHICH IS SHOWN
 FOR HOUSE FOR SHELL FOR SECOND FLOOR WHICH DOES NOT
 SHOW ANY OVER RIDE DEVICES.
 PLEASE ALSO SEE FOR EXAMPLE THE LOBBY AREA WHICH IS
 BEING ILLUMINATED BY LIGHTING IN THE CEILING FROM THE
 2ND FLOOR LIGHTING CONTROL PANEL. WHERE ARE THE OVER
 RIDE DEVICES FOR THE FRONT ENTRANCE AREA? THIS IS AN
 OPEN AREA FOR THE FIRST FLOOR.
 PLEASE CLARIFY CIRCUITING FOR FOUNDATION ROOM,
 CONFERENCE ROOM ON SECOND FLOOR AS THESE ARE SHOWN TO
 CIRCUIT 42 AND ALSO A 42A AND 42B? THIS IS UNCLEAR HOW
 THESE ARE CIRCUITED AS PANEL SCHEDULE IS BEING ASSUMED
 TO BE NHP2. THIS PANEL SCHEDULE ONLY INDICATES ONE #42
 CIRCUIT. *LIGHTING*.
 THE FLOORS ARE REQUIRED TO BE SEPARATED.
 THESE ARE SOME EXAMPLES, AND IN NO WAY NOTES ALL
 POSSIBLE SCENERIOS.
 ** PLEASE SEE THAT THERE ARE SEVERAL AREAS IN WHICH
 LIGHTING CONTROLS ARE NOT YET COMPLETE FOR CHAPTER 13
 AS NOTED.
  
 C) PLEASE SEE THE METHOD OF CALCULATIONS SUBMITTED AS
 *WHOLE BUILDING * METHOD *A* MAY NOT BE USED. THIS IS
 AN EXISTING BUILDING WHICH IS CURRENTLY BEING REMODELED
 UNDER METHOD *B*.
 THIS ALSO FALLS UNDER RENOVATED BUILDINGS PER
 13-101.1.3. PLEASE SEE AS STATED ON PREVIOUS REVIEW THE
 METHOD CALCULATION WOULD DEPEND ON KNOWN FACTORS AND AS
 THERE ARE STILL PORTIONS OF THIS BUILDING NOT
 COMPLETED, METHOD *A* COULD NOT BE USED EITHER PER
 13-101.6.
 PLEASE SUBMIT THE CORRECT METHOD WHICH AS STATED IN THE
 TWO SECTIONS GIVEN COULD BE *B* OR *C*.13-415.1.B.1
 PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS SHALL MEET
 13-415.
 ** PLEASE SEE MECHANICAL COMMENTS AS THIS MAY ALSO BE
 PART OF THEIR REVIEW NOTES.
  
 D) PLEASE SUBMIT COMPLETE INFORMATION FOR LIGHTING
 CONTROL PANELS/SYSTEM BEING PROPOSED. PLEASE SEE THE
 PLANS ONLY FOR A *LIGHTING CONTROL PANEL* WHICH DOES
 NOT PROVIDE THE INFORMATION AS NEEDED FOR COMPLIANCE
 WITH SECTIONS A AND B OF THIS SAME NOTE #2
  
 E) PLEASE PROVIDE NOTE ON PLANS FOR 13-413.1.ABC.2
 WHICH CONTAINS SUB SECTIONS 2.1 AND 2.2.
 THIS WAS RECENTLY CONFIRMED WITH THE FLORIDA BUILDING
 COMMISSION.
  
 3) NOTE: PLANS NOW INDICATE THE PHOTO-METRICS FOR
 EGRESS PATHS FOR NORMAL CONDITIONS, HOWEVER COULD NOT
 LOCATE LEVELS FOR EMERGENCY CONDITIONS. THIS COMMENT IS
 NOT FOR STAIRS AS THE SAME FIXTURES ARE FOR BOTH
 CONDITIONS.
 PLEASE CLARIFY THE EGRESS PATHS FOR CORRIDORS AS THE
 LEVELS ARE DONE SHOWING GENERAL FIXTURES AS WELL AS
 EMERGENCY.
 LS 101 7.8 AND 7.9.
 FAC 61G15-33.004
  
 4) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOMS WHICH
 ARE ON EE-401. PLEASE CLARIFY THE DESIGNATIONS AS ROOM
 #216 IS BEING NOTED FOR 2ND FLOOR HOWEVER 216 ON THE
 SECOND FLOOR IS A CORRIDOR. PLEASE SEE THE ROOM FOR THE
 ELECTRICAL CLOSET IS SHOWN AS 203 ON EL-102. THIS IS A
 MINOR COMMENT HOWEVER AS PLANS ARE COMING BACK FOR
 OTHER COMMENTS, PLEASE CORRECT AT THIS TIME.
  
 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUTES 553.80(2)(B). THERE ARE CODES WHICH
 WERE REPEATED ONCE AGAIN WHICH WERE NOTED THREE TIMES.
 THERE WILL BE A FEE ASSESSED AS REQUIRED BY THE
 STATUTES. THE FEE AMOUNT IS DUE BEFORE PLANS MAY BE
 RESUBMITTED. IT IS RECOMMENDED THAT THE COMMENTS ARE
 GONE OVER BEFORE PLANS ARE RESUBMITTED. ONE COPY OF THE
 ELECTRICAL SHEETS IS BEING RETAINED BY THIS OFFICE.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-29 10:17:40 
  
 REVIEW COMMENCED.
2007-10-27 12:23:512007-10-27 12:23:51
  
 IN ELEC FOR REVIEW


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved