2007-08-14 16:33:48REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS EVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. BUILDING RELIEF SHOULD ONLY BE USED IF A BUILDING IS
 UNDER AN UNUSUALLY HIGH POSITIVE PRESSURE. THIS SYSTEM
 IS NOT BALANCED AS SUCH. THE AIR BALANCE ON FIRST FLOOR
 IS NOW AT -1365 CFM. AN OVERALL NEGATIVE PRESSURE IN
 THE BUILDING IS NOT ALLOWED. THE MECHANICAL SYSTEM
 SHALL BE DESIGNED TO ASSURE THAT THE BUILDING IS
 PRESSURIZED WITH RESPECT TO THE OUTDOORS IN ACCORDANCE
 WITH FBC 13-409.1.ABC.2. PROVIDE AN OVERALL AIR BALANCE
 SCHEDULE FOR THE BUILDING SHOWING COMPLIANCE WITH THIS
 SECTION.
  
 3. OK
  
 4. OK
  
 5. PLEASE SHOW HOW ONE 600 CFM TRANSFER (TD-5 ON
 SCHEDULE) WILL ALLOW FOR 950 CFM OF MAKE-UP AIR. ALSO,
 WHEN THIS COMMENT IS ADDRESSED, PLEASE TAKE INTO
 ACCOUNT THE ISSUE RAISED BY THE LATEST COMMENT #2.
  
 6. OK
  
 7. OK
  
 8. SOME REVISIONS HAVE TAKEN PLACE IN THIS AREA ON
 ARCHITECTURAL PLANS. IT APPEARS THAT A FIRE DAMPER HAS
 BEEN UNNECESSARILY ADDED TO THE OA DUCT THROUGH THE
 WALL BETWEEN ROOMS 150 AND 103. ALSO, A FIRE DAMPER IS
 MISSING IN THE 6X6 SUPPLY DUCT WHICH TERMINATES AT THE
 WALL BETWEEN ROOMS 101 AND 110. AS FOR BALANCED RETURN,
 THERE IS NO EXCEPTION IN FBC,M 601.4 FOR DOORS WITH
 HOLD-OPEN DEVICES. PROVIDE BALANCED RETURN.
  
 9. OK
  
 10. SEE COMMENT #2.
  
 11. THERE ARE DOORS BETWEEN ROOMS 200 AND 201. PROVIDE
 BALANCED RETURN PER FBC,M 601.4.
  
 12. OK
  
 13. OK
  
 14. OK
  
 15. SEE COMMENT #11.
  
 16. OK
  
 17. OK
  
 18. PRODUCT APPROVAL WITH INSTALLATION INSTRUCTIONS
 SHALL BE ON SITE FOR INSPECTION.
  
 19. OK
  
 20. A) PROVIDE TWO SETS OF ENERGY CALCULATIONS, EACH
 WITH THE ORIGINAL SIGNATURE AND SEAL OF THE DESIGNER
 PER FBC 13-103.1.1.1. NO PHOTOCOPIED SIGNATURES OR
 SEALS WILL BE ACCEPTED.
 B) BUILDING OWNER OR OWNER'S ARCHITECT SHALL CERTIFY
 THAT THE BUILDING IS IN COMPLIANCE WITH CHAPTER 13 OF
 THE FBC PER FBC 13-400.3.ABC.2.
 C) VERIFY THAT THE TYPES OF BUILDING COMPONENTS USED IN
 THE INPUT DATA REPORT MATCHES THE TYPES SHOWN ON THE
 PLANS AND/OR THE BUILDING. EXAMPLE: THIS IS NOT A METAL
 BUILDING WITH R-19 BATTS AS IS SHOWN ON ENERGY
 CALCULATIONS. IS THE EXTERIOR OF THIS BUILDING 6" METAL
 STUDS WITH R-13 BATTS?
  
 21. OK
  
 22. PG MC-702 DETAIL 1: NOTE #9, FCU'S SHALL BE SHUT
 DOWN BY DUCT SMOKE DETECTOR OR AREA SMOKE DETECTOR PER
 FBC,M 606.2.1.
  
 23. OK
  