Plan Review Notes For Permit 07040621 |
Permit Number |
07040621 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-09-24 12:28:45 | *****DENIED***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY | | LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102. YOUR | | RESPONSE STILL DOES NOT CLARIFY/IDENTIFY TO DETERMINE | | EMERGENCY LIGHTING | | | | 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION | | 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT | | ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC | | PLEASE ADDRESS/INDICATE COMMENT IN THE PLANS AND/OR | | SPECIFICATIONS | | | | 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF | | ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING | | ELEVATORS). COULD NOT LOCATE ON SHEET EP-101 AND EC-101 | | AS PER YOUR RESPONSE LETTER INDICATES | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|