2007-08-31 12:14:415205 GREENWOOD AVE
 BUILD-OUT3RD REVIEW
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 3RDREVIEW
 ACTION: DENIED
  
 NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED
 PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN
 ADDITION TO THIS STRUCTURE.
 PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE
 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS
 : LEVEL 3 AND CHAP 9 FOR ADDITIONS
 AS WELL AS 2006 FBC BUILDING..
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3-4) COMPLIED.
  
 5) SEMI-COMPLIED.SHEET GV-101 DOOR 174A IS MISSING
 THE 18? ON THE PULL SIDE OF DOOR AT LATCH SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
 6-7A) COMPLIED.
  
 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS
 OR FIRE SPRINKLERS ARE ACTIVATED?
  
 7C)2ND REQUEST. SEMI-COMPLIED, THE DETAIL# 03 ON
 AF-402 IS TO BE 1HR RATED WALL PLEASE PROVIDE THE UL
 NUMBER OR US GYPSUM NUMBER THAT ALLOWS DRYWALL ON ONLY
 ONE SIDE OF THE ASSEMBLY? PLEASE PROVIDE THE COMPLETE
 UL LISTING NUMBER, PROVIDE A DETAIL OF THE UL LISTING
 AND PROVIDE A SECTION OF THE L HOUR RATED WALL.706.3
 FIRE RESISTANCE RATINGS.
  
 7D-9) COMPLIED.
  
 10) 2ND REQUEST,GV-102 ELEVATOR LOBBY 200 INDICATES A
 PAIR OF DOORS AND THE OPPOSITE END OF THIS AREA THERE
 APPEARS TO BE GLASS, IT IS NOT CLEAR IF THIS IS A WALL
 OR IF IT IS A GLASS HANDRAIL, PLEASE PROVIDE A CUT
 THROUGH THIS SECTION. SEE ATRIUM REQUIREMENTS 404.5 SEE
 EXCEPTION (1).THE PLAN ACTUALLY INDICATES THE 1 HR
 RATED WALL TO FALL IN LINE WITH DOOR LINE. SHEET AF-601
 INDICATES DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE
 PROVIDE THIS INFORMATION FOR THESE DOORS AND THE RATED
 DOORS FOR THE FIRST FLOOR.
 SHEET EA101 & EA 102 INDICATE SYMBOLS THAT
 POSSIBLY TIE TO THE ALARM PANEL BUT SHEET
 EC-001 WHICH IS THE FIRE ALARM SYMBOLS AND NOTES IS
 MISSING PLEASE PROVIDE. ADDITIONAL INFORMATION REQUIRED
 106.1.2*.
  
 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN
 ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE
 STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS,
 HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT
 THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN
 THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN
 ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION
 505 .
  
 11A-11B) COMPLIED. SMOKE CONTROL NOT REQUIRED SECTION
 404 EXCEPTIONS.
  
 12-17) COMPLIED.
  
 18)SEMI-COMPLIED, THE FRONTS AND INTERIOR OF THE
 CABINETS ARE TO BE REMOVED FOR FRONTAL APPROACH
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 19-20) COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]