Plan Review Notes
Plan Review Notes For Permit 07040621
Permit Number 07040621
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-27 12:56:21*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.AS PERTAINS TO THE PROJECT CODE DATA ON GV-101,
 REFERENCE THE FOLLOWING:NFPA 1 (2003 EDITION),NFPA
 101 (2003 EDITION),ANDFLORIDA FIRE PREVENTION CODE
 (2004 EDITION).
  
 03.ON SHEET GV-101, EXPLAIN THE DIFFERENCE BETWEEN FE
 AND FHV LEGEND SYMBOLS.BOTH INDICATE FIRE
 EXTINGUISHER.
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 GREENWOOD AVENUE, SHOW/DISPLAY THE NUMERICAL ADDRESS ON
 THE BUILDING.PLEASE BE REMINDED EVEN A MARKEE OR
 MONUMENT SIGN IS USED AT GREENWOOD AVENUE, THE
 NUMERICAL ADDRESS SHALL BE ON THE STRUCTURE AS PER WEST
 PALM BEACH ADDRESSING CODE.
  
 05.PLANS INDICATE THAT THIS BUILDING WILL BE FIRE
 SPRINKLERED IN CONJUNCTION WITH A FIRE ALARM SYSTEM.
 SHOW THE LOCATION OF THE REQUIRED PREMISES ACCESS/KNOX
 BOX AT THE APPROPIATE EXTERIOR ELEVATION.FOR
 APPLICATIONS, CONTACT THE WPB FIRE PREVENTION AT
 561-804-4724.
  
 06.ON SHEET GV-102,EXPLAIN THE USE OF THE SLEEP
 ROOM (226).
  
 07.ON SHEET GV-102, EXPLAIN THE AREA LOCATED IN THE
 TOP RIGTH CORNER IN THE CONFERENCE PRESENTATION ROOM
 (210).HOW IS ACESS GAINED?
  
 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY
 LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102.
  
 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION
 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT
 ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC
  
 10.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS
 CORRIDORS;SHALL BE CLASS A, CLASS B, OR CLASS C IN
 ALL OTHER AREAS.
  
 11.ON SHEET FS-101, INDICATE FROM WHOM THE FIRE FLOW
 DATA WAS OBTAINED.
  
 12.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL AND FIRE ALARM SYSTEMS SCOPE OF
 WORK.
  
 13.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 14.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 15.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 16.DOORS AS A MEANS OF EGRESS COMPONENT SHALL COMPLY
 WITH SECTION 7.2.1 OF NFPA 101.
  
 17.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LOCK OR LATCH IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE.
  
 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF
 ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING
 ELEVATORS).
  
 19.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE)
 ARE REQUIRED IN THE ELEVATOR LOBBIES.
  
 20.ALL FIRE DOORS AND WINDOWS TO COMPLY WITH NFPA 80,
 FIRE DOORS AND WINDOWS.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW