2007-04-26 15:59:54 | ** UNSAT ** |
| |
| ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT |
| CORRECT. |
| PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN |
| OCT 1ST OF 2005. PLEASE SEEMOST OF THE CODES ARE |
| STILL FROM THE 2001 CODE AND ADOPTED STANDARDS AND |
| CODES FROM THAT TIME. THERE ARE SEVERAL CODES WHICH ARE |
| STILL BEING REFLECTED FROM THE *2001 FBC* , THE 2000 |
| FLORIDA ACCESSIBILITY CODE ETC? |
| PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE |
| CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC. |
| PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING |
| BUILDING ETC. |
| PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO |
| ADOPTED THE NEW 2005 NFPA-70 (NEC). |
| PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE |
| REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS |
| SHOWN AS THE 2002. |
| PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL |
| COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005 |
| NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1. |
| |
| ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY |
| ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL |
| REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED |
| FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF |
| THE OTHER TRADES. |
| |
| 2) NOTE: PLEASE KNOW THAT IT IS MOST IMPORTANT TO |
| COORDINATE PLANS WITH THE PLANS WHICH WERE SUBMITTED |
| FOR SHELL BUILDING AND ADDITION. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 3) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS WERE |
| SUBMITTED FOR THE BUILD OUT OF SPACE. |
| PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED |
| FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD |
| FOR SHELL PERMIT WOULD CHANGE. |
| PLEASE SEE THAT NO REVIEW OF CODE COMPLIANCE CAN BE |
| DONE AT THIS TIME. PLEASE BE SURE TO COORDINATE ALL |
| FIXTURES, FIXTURE WATTAGES, TYPE OF FIXTURES, CONTROLS |
| AND NUMBER OF FIXTURES BETWEEN PLANS AND ENERGY |
| CALCULATIONS. |
| PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR |
| LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE |
| 2004 FBC. |
| PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE |
| NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED |
| PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT |
| INDICATE ANY CONTROL FOR LIGHTING AT ALL. |
| PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS |
| OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE |
| COMPLIANCE. |
| PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR |
| INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER |
| RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT |
| COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE |
| REVIEWED. |
| 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1, |
| 13-415.2 |
| PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND |
| SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG |
| WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS. THESE |
| WOULD BE INCORPORATED IN PLAN SETS NOT SUBMITTED AS |
| LOOSE SHEETS.13-103.1.1.1 |
| |
| ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE |
| COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MOST ITEMS |
| REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY |
| BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION |
| WAS NOT SUBMITTED. |
| PLEASE SEE CHAPTER 13 IN THE 2004 FBC . |
| |
| 4) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE |
| REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED |
| ON SHELL/ADDITION PLANS. AS THE SHELL/ADDITION PLANS |
| ARE NOT ISSUED AT THIS TIME AND DO NOT INDICATE |
| COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER NFPA-101 |
| 7.8.1.3, 7.9.2.2 |
| PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION |
| PERMIT. |
| |
| 5) NOTE: PLEASE SEE THAT THE RISER ON SHELL/ADDITION |
| PERMIT HAS NOTES WHICH REQUIRES CHANGES. |
| PLEASE SEE THERE IS MORE INFORMATION TO BE SUBMITTED |
| WITH MORE COMPLETEDINFORMATION FOR CONDUCTORS, |
| CONDUITS ETC, HOWEVER THERE ARE STILL SOME ITEMS WHICH |
| NEED TO BE INCLUDED FOR CODE COMPLIANCE AS PREVIOUSLY |
| NOTED. |
| PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE |
| AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT |
| BE REVIEWED FOR CODE COMPLIANCE. |
| PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, |
| SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC |
| RATINGS FOR ALL SERVICE EQUIPMENT ETC. |
| ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL |
| MISSING. |
| A) NO GROUNDING ELECTRODE SYSTEM. |
| B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT. |
| C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE |
| INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW |
| SHOWN ON RISER. (250.6, 250.24) |
| D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN |
| WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS |
| ETC SHOWN ARE OF ADEQUATE SIZE ETC. |
| SECTIONS AS GIVEN IN PREVIOUS REVIEW. |
| ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, |
| 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, |
| 110.26 ETC. |
| PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. |
| |
| 6) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE |
| IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED |
| FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS |
| NOTED ON PREVIOUS REVIEW. |
| ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE |
| SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL |
| PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS |
| NOT ACCEPTABLE TO THIS AHJ. |
| 110.3, 90.4. |
| |
| 7) NOTE:PLEASE SEE NOTE UNDER SHELL/ADDITION PERMIT |
| WITH RESPECT TO LOAD CALCULATIONS. |
| PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR PANEL NHP |
| DOES NOT PROVIDE THE REQUIRED AND REQUESTED INFORMATION |
| FOR COMPLETE LOAD CALCULATIONS FOR SERVICE AND ALL |
| EQUIPMENT BY THE DESIGNER OF RECORD.ALL INFORMATION |
| SHALL BE INCLUDED IN RECORD SETS OF PLANS AND NOT |
| SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN THE |
| COMPLETED INFORMATION OR DONE BY THE DESIGNER OR |
| RECORD. |
| PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12, |
| 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS |
| PREVIOUSLY NOTED. |
| PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE |
| AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING |
| SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL |
| SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD |
| SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD |
| CALCULATIONS FOR THIS PANEL OR SERVICE. |
| PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR |
| CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| NOT BE DETERMINED AT THIS TIME. |
| PLEASE SEE ALL OF 220. |
| PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| LOADS AND LARGEST MOTORS LOADS AT 125%. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| 8) NOTE:THIS IS ONE OF THE SAME NOTES UNDER BASE |
| BUILDING/SHELL PLANS. |
| PLEASE SEE THIS SAME COMMENT FROM PREVIOUS REVIEW WHICH |
| REMAINS AS NOT INFORMATION WAS SUBMITTED. PLEASE SEE |
| NOTE ABOVE (#13) WHICH REQUEST THE AIC RATINGS FOR ALL |
| EQUIPMENT. PLEASE BE SURE THESE CORRELATE WITH THE |
| DIVISION SPEC SUBMITTED. 106.1.2. NEC 110.9 |
| |
| 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| SHEETS SUBMITTED. |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| SETS. |
| FBC 106.3.5.1.2 |
| |
| 10) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE SECURITY |
| PLANS FOR CAMERAS ETC ARE TO BE UNDER SEPARATE |
| PERMITS. |
| |
| 11) NOTE: PLEASE COMPETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE |
| SURE TO SEE PREVIOUS PLANS FOR SHELL BUILDING AND |
| CIRCUITING PER 700.12E FOR ALL EMERGENCY AND EXIT |
| LIGHTS. |
| 106.1.2, |
| 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM |
| THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS |
| ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES |
| SPECIFIC. |
| |
| **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| REQUIRED BY THIS SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |