Plan Review Notes
Plan Review Notes For Permit 07040621
Permit Number 07040621
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-26 15:59:54** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE SEEMOST OF THE CODES ARE
 STILL FROM THE 2001 CODE AND ADOPTED STANDARDS AND
 CODES FROM THAT TIME. THERE ARE SEVERAL CODES WHICH ARE
 STILL BEING REFLECTED FROM THE *2001 FBC* , THE 2000
 FLORIDA ACCESSIBILITY CODE ETC?
 PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE
 CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC.
 PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING
 BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE
 REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS
 SHOWN AS THE 2002.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL
 REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED
 FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF
 THE OTHER TRADES.
  
 2) NOTE: PLEASE KNOW THAT IT IS MOST IMPORTANT TO
 COORDINATE PLANS WITH THE PLANS WHICH WERE SUBMITTED
 FOR SHELL BUILDING AND ADDITION.
 FBC 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS WERE
 SUBMITTED FOR THE BUILD OUT OF SPACE.
 PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED
 FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD
 FOR SHELL PERMIT WOULD CHANGE.
 PLEASE SEE THAT NO REVIEW OF CODE COMPLIANCE CAN BE
 DONE AT THIS TIME. PLEASE BE SURE TO COORDINATE ALL
 FIXTURES, FIXTURE WATTAGES, TYPE OF FIXTURES, CONTROLS
 AND NUMBER OF FIXTURES BETWEEN PLANS AND ENERGY
 CALCULATIONS.
 PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR
 LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE
 2004 FBC.
 PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE
 NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED
 PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT
 INDICATE ANY CONTROL FOR LIGHTING AT ALL.
 PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS
 OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE
 COMPLIANCE.
 PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR
 INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER
 RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT
 COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE
 REVIEWED.
 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1,
 13-415.2
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
 THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND
 SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG
 WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS. THESE
 WOULD BE INCORPORATED IN PLAN SETS NOT SUBMITTED AS
 LOOSE SHEETS.13-103.1.1.1
  
 ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE
 COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MOST ITEMS
 REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION
 WAS NOT SUBMITTED.
 PLEASE SEE CHAPTER 13 IN THE 2004 FBC .
  
 4) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE
 REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED
 ON SHELL/ADDITION PLANS. AS THE SHELL/ADDITION PLANS
 ARE NOT ISSUED AT THIS TIME AND DO NOT INDICATE
 COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER NFPA-101
 7.8.1.3, 7.9.2.2
 PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION
 PERMIT.
  
 5) NOTE: PLEASE SEE THAT THE RISER ON SHELL/ADDITION
 PERMIT HAS NOTES WHICH REQUIRES CHANGES.
 PLEASE SEE THERE IS MORE INFORMATION TO BE SUBMITTED
 WITH MORE COMPLETEDINFORMATION FOR CONDUCTORS,
 CONDUITS ETC, HOWEVER THERE ARE STILL SOME ITEMS WHICH
 NEED TO BE INCLUDED FOR CODE COMPLIANCE AS PREVIOUSLY
 NOTED.
 PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL
 MISSING.
 A) NO GROUNDING ELECTRODE SYSTEM.
 B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT.
 C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE
 INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW
 SHOWN ON RISER. (250.6, 250.24)
 D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN
 WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS
 ETC SHOWN ARE OF ADEQUATE SIZE ETC.
 SECTIONS AS GIVEN IN PREVIOUS REVIEW.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 6) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE
 IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED
 FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS
 NOTED ON PREVIOUS REVIEW.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 7) NOTE:PLEASE SEE NOTE UNDER SHELL/ADDITION PERMIT
 WITH RESPECT TO LOAD CALCULATIONS.
 PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR PANEL NHP
 DOES NOT PROVIDE THE REQUIRED AND REQUESTED INFORMATION
 FOR COMPLETE LOAD CALCULATIONS FOR SERVICE AND ALL
 EQUIPMENT BY THE DESIGNER OF RECORD.ALL INFORMATION
 SHALL BE INCLUDED IN RECORD SETS OF PLANS AND NOT
 SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN THE
 COMPLETED INFORMATION OR DONE BY THE DESIGNER OR
 RECORD.
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING
 SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL
 SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD
 SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD
 CALCULATIONS FOR THIS PANEL OR SERVICE.
 PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 8) NOTE:THIS IS ONE OF THE SAME NOTES UNDER BASE
 BUILDING/SHELL PLANS.
 PLEASE SEE THIS SAME COMMENT FROM PREVIOUS REVIEW WHICH
 REMAINS AS NOT INFORMATION WAS SUBMITTED. PLEASE SEE
 NOTE ABOVE (#13) WHICH REQUEST THE AIC RATINGS FOR ALL
 EQUIPMENT. PLEASE BE SURE THESE CORRELATE WITH THE
 DIVISION SPEC SUBMITTED. 106.1.2. NEC 110.9
  
 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE SECURITY
 PLANS FOR CAMERAS ETC ARE TO BE UNDER SEPARATE
 PERMITS.
  
 11) NOTE: PLEASE COMPETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE
 SURE TO SEE PREVIOUS PLANS FOR SHELL BUILDING AND
 CIRCUITING PER 700.12E FOR ALL EMERGENCY AND EXIT
 LIGHTS.
 106.1.2,
 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS
 ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES
 SPECIFIC.
  
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717