2007-05-30 16:57:08 | BUILDING PLAN REVIEW |
| PERMIT: 07040621 |
| ADD: 5205 GREENWOOD |
| CONT: HEDRICK BROTHERS |
| TEL: (561)689-8880 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| |
| NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED |
| PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN |
| ADDITION TO THIS STRUCTURE. |
| PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE |
| 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS |
| : LEVEL 3 AND CHAP 9 FOR ADDITIONS |
| AS WELL AS 2006 FBC BUILDING.. |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY |
| COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| SUCH NOTICE IS NULL & VOID. |
| NOTE: 713.13(6)THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION |
| SITE BEFORE THE FIRST INSPECTION. |
| |
| 3A) SHEET GV-101 TYPE OF CONSTRUCTION: IV HEAVY TIMBER |
| PLEASE LOOK AT |
| SECTION 602 FOR BUILDING CONSTRUCTION CLASSIFICATIONS |
| AND TABLE 503.THIS BUILDING IS NOT |
| A HEAVY TIMBER DESIGN. NOTE IF IT IS AN "A OR B" |
| CLASSIFICATION. |
| |
| 3B) GV-101 INDICATES 9006 SQ FT FIRST FLOOR WHILE THE |
| 2ND FLOOR HAS 9170, THE FOOTPRINT ON THE FIRST FLOOR IS |
| LARGER HAVING MORE ARERA, PLEASE RECALCULATE PLUS |
| COVERED WALKWAY! |
| |
| 3C) NOTE INCREASES THAT CAN BE TAKEN FOR A FULLY |
| SPRINKLERED BUILDING(AREA INCREASES)! |
| |
| 4) PLANS ALSO INDICATE THE BUILDING DESIGN IS THE 2004 |
| FBC, PLANS SUBMITTED |
| AFTER DEC 12,2006 FALL IN UNDER THE 2006 FBC. |
| |
| 5)SHEET GV-101 INDICATES DOORWAYS IN THE CORRIDOR |
| THAT DO NOT HAVE IDENTIFYING TAGS, THE FIRST DOOR ISUE |
| |
| IS LOCATED BETWEEN ROOM 167 AND ROOM 171, THE SECOND |
| DOOR IS LOCATED BETWEEN |
| ROOMS 193 AND 125B. IN BOTH CASES IT APPEARS THERE IS |
| NOT 18" ON THE LATCH SIDE OF THE DOORWAY. 11-4.13.6 |
| MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| CLEARANCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL |
| BE AS SHOWN IN FIG. 25. THE FLOOR OR |
| GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 6)PLANS INDICATE THIS IS A BUSINESS OCCUPANCY, THE |
| PLANS DO NOT IDENTIFY IF IT IS A SINGLE TENANT? THE |
| FIRST FLOOR DOES HAVE TWO |
| WAITING ROOMS 110 AND 150? 106.1.2* ADD INFO REQUIRED |
| AND708.1(5). |
| |
| 7) GV-102 THE PLANS INDICATE ON THE MAIN ENTRY STAIR |
| WITH ACOILING FIRE RATED DOOR AT THE HEAD OF THE |
| SECOND STORY LANDING AND WHAT APPEARS TO BE A 1 HOUR |
| RATED WALL. |
| SHEET AF-402 DETAIL 03 INDICATES A HORIZONTAL COILING |
| FIRE DOOR. |
| 7A) PLEASE SUBMIT PRODUCT INFORMATION FOR A 1 HR RATED |
| ASSEMBLY. |
| 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS |
| OR FIRE SPRINKLERS ARE ACTIVATED? |
| 7C) THE DETAIL# 03 ON AF-402 IS TO BE 1HR RATED WALL |
| PLEASE PROVIDE THE UL NUMBER OR US GYPSUM NUMBER THAT |
| ALLOWS DRYWALL ON ONLY ONE SIDE OF THE ASSEMBLY? 7D) |
| PLEASE INDICATE HOW ONE WOULD GAIN ACCESS TO DO |
| MAINTENCE WORK ON THE COILED FIRE DOOR ? ADDITIONAL |
| COMMENTS MAY APPEAR ON THESE ITEMS ONCE THE RESPONCES |
| ARE REVIEWED. |
| |
| 8)GV-102 PLANS APPEAR TO HAVE A SLEEP STUDY AREA WITH |
| A CONTROL ROOM. PLEASE PROVIDE ADDITIONAL INFORMATION |
| AS TOTHE FUCTION OF THIS AREA? WILL THE PATIENTS BE |
| THERE OVER 24 HRS? |
| WILL THE PATIENTS BE MEDICATED? AND WILL THERE BE MORE |
| THAN ONE PATEINT THERE SLEEPING? |
| |
| 9)GV-102 ROOM 210 CONFERENCE PRESENTATION THERE |
| APPEARS TO BE A SEPERATE ROOM IN THE UPPER RIGHT CORNER |
| WITH NO IDENTIFICATION? PLEASE PROVIDE ADDITIONAL |
| INFORMATION. 106.1.2* |
| |
| 10) GV-102 ELEVATOR LOBBY 200 INDICATES A PAIR OF DOORS |
| AND THE OPPOSITE END OF THIS AREA THERE APPEARS TO BE |
| GLASS, IT IS NOT CLEAR IF THIS IS A WALL OR IF IT IS A |
| GLASS HANDRAIL, PLEASE PROVIDE A CUT THROUGH THIS |
| SECTION. SEE ATRUIM REQUIREMENTS 404.5 SEE EXCEPTION |
| (1).THE PLAN ACTUALLY INDICATES THE 1 HR RATED WALL |
| TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 INDICATES |
| DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE PROVIDE |
| THIS INFORMATION FOR THESE DOORS AND THE RATED DOORS |
| FOR THE FIRST FLOOR. |
| |
| 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN |
| ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE |
| STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS, |
| HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL, |
| AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT |
| THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN |
| THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN |
| ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION |
| 505 . |
| |
| 11A)404.4 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL |
| BE INSTALLED IN ACCORDANCE WITH SECTION 909 . |
| 11B)404.6 STANDBY POWER. EQUIPMENT REQUIRED TO |
| PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO A STANDBY |
| POWER SYSTEM IN ACCORDANCE WITH SECTION 909.11 . |
| |
| 12) GV-102ROOM 223 PLEASE SHOW THE CLEAR FLOOR SPACE |
| REQUIRED FOR PLUMBING FIXTURES, IT APPEARS THAT THE |
| DOORWAY MAY SWING INTO THE LAV CLEAR FLOOR SPACE. |
| 11-4.19.3 CLEAR FLOOR SPACE . |
| A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY |
| 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD |
| APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR |
| OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM |
| OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE |
| FIGURE 32 ). |
| |
| 13) GV-102 ROOM XXX SHELL IS THIS THE SAME TENANT |
| SPACE? |
| |
| 14)PLEASE DEVELOP A DOOR IDENIFICATION SYSTEM NO |
| DOORS ARE IDENTIFIED ON EITHER FLOOR. |
| |
| 15) GV-102 CONFERENCE ROOM 210 HAS AN OCCUPANT LOAD OF |
| APPROX 114 PEOPLE PLEASE SEE TABLE 1016.1 FOR ASSEMBLY |
| OCCUPANCIES, OCCUPANT LOADS SERVED BY CORRIDORS, TABLE |
| 1016.1WITH SPRINKLERS SYSTEMS AND OCCUPANT LOADS >30 |
| REQUIRING 1 HR RATED CORRIDORS. |
| |
| 16) GV-102 ROOM 211 ELEVATOR MACHINE ROOM. 3006.4 |
| MACHINE ROOMS AND MACHINERY SPACES. |
| ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE |
| ENCLOSED WITH CONSTRUCTION HAVING A FIRE-RESISTANCE |
| RATING NOT LESS THAN THE REQUIRED RATING OF THE |
| HOISTWAY ENCLOSURE SERVED BY THE MACHINERY. OPENINGS |
| SHALL BE PROTECTED WITH ASSEMBLIES HAVING A |
| FIRE-RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR |
| THE HOISTWAY ENCLOSURE DOORS. |
| |
| 17) GV-102 ROOM 211 3006.1 ACCESS.AN APPROVED MEANS |
| OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS . |
| AN APPROVED ACCESS DOES NOT HAVE MEANS OF EGRESS |
| THROUGH TENANT SPACES. |
| |
| 18)AF-210 LOUNGE SINK IS CABINET ELEVATION INDICATES |
| A 3'-0" ELEVATION. SINKS:11-4.24.2 SINKS, HEIGHT. |
| SINKS SHALL BE MOUNTED WITH THE COUNTER NO HIGHER THAN |
| 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| AT LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK. |
| |
| 19) AF-320 VARIOUS WALLS INDICATE THAT SOME MAY REQUIRE |
| FIRE RATINGS, PLEASE PROVIDEINFORMATION ON THE FLOOR |
| TO FLOOR ORFLOOR TO ROOF/ CEILING ASSEMBLIES. 713.1 |
| GENERAL. JOINTS INSTALLED IN OR BETWEEN |
| FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING |
| ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME |
| PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE |
| RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH |
| IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE |
| TESTED IN ACCORDANCE WITH SECTION 713.3 . THE VOID |
| CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY |
| AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 713.4 . |
| |
| 20) AF-401 GRAND STAIR SECTION AT THE TOP OF THE |
| STAIRCASE THE HORIZONTAL PROJECTION OFTHE HANDRAIL IS |
| TO BE A MINIMUM OF 1'-0" LONG. 11-4.9.4 |
| |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |