2007-05-30 16:57:08BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED
 PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN
 ADDITION TO THIS STRUCTURE.
 PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE
 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS
 : LEVEL 3 AND CHAP 9 FOR ADDITIONS
 AS WELL AS 2006 FBC BUILDING..
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3A) SHEET GV-101 TYPE OF CONSTRUCTION: IV HEAVY TIMBER
 PLEASE LOOK AT
 SECTION 602 FOR BUILDING CONSTRUCTION CLASSIFICATIONS
 AND TABLE 503.THIS BUILDING IS NOT
 A HEAVY TIMBER DESIGN. NOTE IF IT IS AN "A OR B"
 CLASSIFICATION.
  
 3B) GV-101 INDICATES 9006 SQ FT FIRST FLOOR WHILE THE
 2ND FLOOR HAS 9170, THE FOOTPRINT ON THE FIRST FLOOR IS
 LARGER HAVING MORE ARERA, PLEASE RECALCULATE PLUS
 COVERED WALKWAY!
  
 3C) NOTE INCREASES THAT CAN BE TAKEN FOR A FULLY
 SPRINKLERED BUILDING(AREA INCREASES)!
  
 4) PLANS ALSO INDICATE THE BUILDING DESIGN IS THE 2004
 FBC, PLANS SUBMITTED
 AFTER DEC 12,2006 FALL IN UNDER THE 2006 FBC.
  
 5)SHEET GV-101 INDICATES DOORWAYS IN THE CORRIDOR
 THAT DO NOT HAVE IDENTIFYING TAGS, THE FIRST DOOR ISUE
  
 IS LOCATED BETWEEN ROOM 167 AND ROOM 171, THE SECOND
 DOOR IS LOCATED BETWEEN
 ROOMS 193 AND 125B. IN BOTH CASES IT APPEARS THERE IS
 NOT 18" ON THE LATCH SIDE OF THE DOORWAY. 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR
 GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 6)PLANS INDICATE THIS IS A BUSINESS OCCUPANCY, THE
 PLANS DO NOT IDENTIFY IF IT IS A SINGLE TENANT? THE
 FIRST FLOOR DOES HAVE TWO
 WAITING ROOMS 110 AND 150? 106.1.2* ADD INFO REQUIRED
 AND708.1(5).
  
 7) GV-102 THE PLANS INDICATE ON THE MAIN ENTRY STAIR
 WITH ACOILING FIRE RATED DOOR AT THE HEAD OF THE
 SECOND STORY LANDING AND WHAT APPEARS TO BE A 1 HOUR
 RATED WALL.
 SHEET AF-402 DETAIL 03 INDICATES A HORIZONTAL COILING
 FIRE DOOR.
 7A) PLEASE SUBMIT PRODUCT INFORMATION FOR A 1 HR RATED
 ASSEMBLY.
 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS
 OR FIRE SPRINKLERS ARE ACTIVATED?
 7C) THE DETAIL# 03 ON AF-402 IS TO BE 1HR RATED WALL
 PLEASE PROVIDE THE UL NUMBER OR US GYPSUM NUMBER THAT
 ALLOWS DRYWALL ON ONLY ONE SIDE OF THE ASSEMBLY? 7D)
 PLEASE INDICATE HOW ONE WOULD GAIN ACCESS TO DO
 MAINTENCE WORK ON THE COILED FIRE DOOR ? ADDITIONAL
 COMMENTS MAY APPEAR ON THESE ITEMS ONCE THE RESPONCES
 ARE REVIEWED.
  
 8)GV-102 PLANS APPEAR TO HAVE A SLEEP STUDY AREA WITH
 A CONTROL ROOM. PLEASE PROVIDE ADDITIONAL INFORMATION
 AS TOTHE FUCTION OF THIS AREA? WILL THE PATIENTS BE
 THERE OVER 24 HRS?
 WILL THE PATIENTS BE MEDICATED? AND WILL THERE BE MORE
 THAN ONE PATEINT THERE SLEEPING?
  
 9)GV-102 ROOM 210 CONFERENCE PRESENTATION THERE
 APPEARS TO BE A SEPERATE ROOM IN THE UPPER RIGHT CORNER
 WITH NO IDENTIFICATION? PLEASE PROVIDE ADDITIONAL
 INFORMATION. 106.1.2*
  
 10) GV-102 ELEVATOR LOBBY 200 INDICATES A PAIR OF DOORS
 AND THE OPPOSITE END OF THIS AREA THERE APPEARS TO BE
 GLASS, IT IS NOT CLEAR IF THIS IS A WALL OR IF IT IS A
 GLASS HANDRAIL, PLEASE PROVIDE A CUT THROUGH THIS
 SECTION. SEE ATRUIM REQUIREMENTS 404.5 SEE EXCEPTION
 (1).THE PLAN ACTUALLY INDICATES THE 1 HR RATED WALL
 TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 INDICATES
 DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE PROVIDE
 THIS INFORMATION FOR THESE DOORS AND THE RATED DOORS
 FOR THE FIRST FLOOR.
  
 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN
 ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE
 STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS,
 HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT
 THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN
 THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN
 ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION
 505 .
  
 11A)404.4 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL
 BE INSTALLED IN ACCORDANCE WITH SECTION 909 .
 11B)404.6 STANDBY POWER. EQUIPMENT REQUIRED TO
 PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO A STANDBY
 POWER SYSTEM IN ACCORDANCE WITH SECTION 909.11 .
  
 12) GV-102ROOM 223 PLEASE SHOW THE CLEAR FLOOR SPACE
 REQUIRED FOR PLUMBING FIXTURES, IT APPEARS THAT THE
 DOORWAY MAY SWING INTO THE LAV CLEAR FLOOR SPACE.
 11-4.19.3 CLEAR FLOOR SPACE .
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 32 ).
  
 13) GV-102 ROOM XXX SHELL IS THIS THE SAME TENANT
 SPACE?
  
 14)PLEASE DEVELOP A DOOR IDENIFICATION SYSTEM NO
 DOORS ARE IDENTIFIED ON EITHER FLOOR.
  
 15) GV-102 CONFERENCE ROOM 210 HAS AN OCCUPANT LOAD OF
 APPROX 114 PEOPLE PLEASE SEE TABLE 1016.1 FOR ASSEMBLY
 OCCUPANCIES, OCCUPANT LOADS SERVED BY CORRIDORS, TABLE
 1016.1WITH SPRINKLERS SYSTEMS AND OCCUPANT LOADS >30
 REQUIRING 1 HR RATED CORRIDORS.
  
 16) GV-102 ROOM 211 ELEVATOR MACHINE ROOM. 3006.4
 MACHINE ROOMS AND MACHINERY SPACES.
 ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE
 ENCLOSED WITH CONSTRUCTION HAVING A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED RATING OF THE
 HOISTWAY ENCLOSURE SERVED BY THE MACHINERY. OPENINGS
 SHALL BE PROTECTED WITH ASSEMBLIES HAVING A
 FIRE-RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR
 THE HOISTWAY ENCLOSURE DOORS.
  
 17) GV-102 ROOM 211 3006.1 ACCESS.AN APPROVED MEANS
 OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS .
 AN APPROVED ACCESS DOES NOT HAVE MEANS OF EGRESS
 THROUGH TENANT SPACES.
  
 18)AF-210 LOUNGE SINK IS CABINET ELEVATION INDICATES
 A 3'-0" ELEVATION. SINKS:11-4.24.2 SINKS, HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER NO HIGHER THAN
 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 AT LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 19) AF-320 VARIOUS WALLS INDICATE THAT SOME MAY REQUIRE
 FIRE RATINGS, PLEASE PROVIDEINFORMATION ON THE FLOOR
 TO FLOOR ORFLOOR TO ROOF/ CEILING ASSEMBLIES. 713.1
 GENERAL. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 713.3 . THE VOID
 CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY
 AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713.4 .
  
 20) AF-401 GRAND STAIR SECTION AT THE TOP OF THE
 STAIRCASE THE HORIZONTAL PROJECTION OFTHE HANDRAIL IS
 TO BE A MINIMUM OF 1'-0" LONG. 11-4.9.4
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  