Plan Review Notes For Permit 07040618 |
Permit Number |
07040618 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-05-30 09:59:16 | *****DENIED***** | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEED TO BE ADDRESSED: | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | COMMENT TO SHEET A-210 | | | | 5.ON SHEET ID-1, SPECIFY THE INTERIOR FINISH | | CLASSIFICATION FOR THE WALLS AND CEILINGS.AS PER NFPA | | 101, THE WALL AND CEILING FINISHES SHALL BE CLASS A OR | | CLASS B IN EXITS AND EXIT CORRIDORS AND CLASS A, CLASS | | B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFIC | | | | NEW COMMENT | | | | 1.SHEET ID-1 SHALL BE SIGNED AND SEALED SINCE IT | | CONTAINS CODE COMPLIANCE INFORMATION. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|