Plan Review Notes
Plan Review Notes For Permit 07040618
Permit Number 07040618
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-30 12:52:06*****DENIED*****
  
  
 1.ONTHE TITLE SHEET UNDER LIFE SAFETY CODE, MAKE
 REFERENCE TO THE 2003 EDITION OF NFPA 101.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.ALL REQUIRED EXIT COMPONENTS SHALL BE MAINTAINED.
 THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF NEW
 BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE OR
 HINDER EGRESS TO OR EXIT FROM THE 6TH FLOOR OR ANY
 OTHER FLOOR IN THE BUILDING.
  
 5.ON SHEET ID-1, SPECIFY THE INTERIOR FINISH
 CLASSIFICATION FOR THE WALLS AND CEILINGS.AS PER NFPA
 101, THE WALL AND CEILING FINISHES SHALL BE CLASS A OR
 CLASS B IN EXITS AND EXIT CORRIDORS AND CLASS A, CLASS
 B, OR CLASS C IN ALL OTHER AREAS.
  
 6. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HO/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722