Plan Review Notes For Permit 07040618 |
Permit Number |
07040618 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-30 12:52:06 | *****DENIED***** | | | | | | 1.ONTHE TITLE SHEET UNDER LIFE SAFETY CODE, MAKE | | REFERENCE TO THE 2003 EDITION OF NFPA 101. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 4.ALL REQUIRED EXIT COMPONENTS SHALL BE MAINTAINED. | | THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF NEW | | BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE OR | | HINDER EGRESS TO OR EXIT FROM THE 6TH FLOOR OR ANY | | OTHER FLOOR IN THE BUILDING. | | | | 5.ON SHEET ID-1, SPECIFY THE INTERIOR FINISH | | CLASSIFICATION FOR THE WALLS AND CEILINGS.AS PER NFPA | | 101, THE WALL AND CEILING FINISHES SHALL BE CLASS A OR | | CLASS B IN EXITS AND EXIT CORRIDORS AND CLASS A, CLASS | | B, OR CLASS C IN ALL OTHER AREAS. | | | | 6. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | FIRE SPRINKLER REMODEL. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HO/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|