Text |
2007-08-11 07:27:19 | |
| |
| |
| DENIED |
| |
| THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE |
| FIRST REVIEW: |
| |
| 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC*.DUE TO INCREASED VALUE, RADON FEES AND |
| NSF RETURNED CHECK ******$ 585.62 SHALL BE PAID BEFORE |
| FURTHER REVIEW.******* |
| ****NOT PERFORMED***** |
| |
| 3)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SETS OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561) 233-5025 FOR MOREINFORMATION. |
| ****NOT PERFORMED***** |
| |
| 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| ****NOT PERFORMED***** |
| |
| 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD |
| ****NOTE THESE SETS ARE NOT THE ENGINEERED SIGNED AND |
| SEALED SET BUT THIS WILL NOT HOLD UP ISSUANCE OF PERMIT |
| AS THEY CAN BE GIVEN TO INSPECTOR ON SITE***** |
| |
| 8)SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| ****ONLY ONE SET WAS SUBMITTED****** |
| |
| NEW COMMENTS |
| |
| 1)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| DRAWINGS. )PLANS AND SPECIFICATIONS DESIGN PARAMETERS |
| SHALL COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| AMENDMENTS PER 106.1.1 FBC* |
| |
| 2)PROVIDE PRODUCT APPROVALS FOR THE (2) SINGLE FRENCH |
| DOORS ON THE FRONT OF BUILDING AND THE DOUBLE SET AT |
| THE REAR |
| |
| 3)PROVIDE THE CORRECT FLORIDA STATEWIDE PRODUCT |
| APPROVAL COVERS AND MIAMI-DADE NOA (03-0605.05) THAT |
| VALIDATES THE CASTCRETE LINTELS |
| |
| 4)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH ADMINISTRATIVE |
| AMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| FBC RES. = FLORIDA BUILDING CODE |
| RESIDENTIAL 2004 C/W 2006 AMENDMENTS |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |