Plan Review Notes
Plan Review Notes For Permit 07040598
Permit Number 07040598
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-18 09:04:29 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 5} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C). AND 210.8(A)(6) GFI. CHECK PLAN
 FOR SPACING REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  