Date |
Text |
2007-06-09 15:11:43 | |
| |
| DENIED |
| |
| 1)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| ADDED TO THE PERMIT APPLICATION FEES |
| |
| 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC*.DUE TO INCREASED VALUE RADON FEES AND |
| NSF RETURNED CHECK $ 585.62 SHALL BE PAID BEFORE |
| FURTHER REVIEW. |
| |
| 3)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SETS OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561) 233-5025 FOR MOREINFORMATION. |
| |
| 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| EACH PRODUCT APPROVAL THAT |
| IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA |
| STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT |
| LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE |
| PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND |
| THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON |
| WWW.FLORIDABUILDING.ORG |
| |
| 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD |
| |
| 7)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION,NATURE, AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1 |
| FBC*. PLEASE NOTE THAT PAGE 4 OF 4 IS ILLEGIBLE. |
| |
| 8)SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| |
| 9)PROVIDE EXISTING LAYOUT OF BUILDING, SHOW ALL WALLS |
| TO BE DEMOLISHED AND WHICH WALLS WILL BE REBUILT ON NEW |
| FLOOR PLAN. SHOW ALL CHANGES IN CONFIGURATION IF ANY. |
| |
| 10)WALL SECTION OF FAMILY ROOM ON PAGE 4/4 SHOWS 2X6 |
| WALL WHICH WOULD REQUIRE R19 INSULATION, ALSO PROVIDE |
| CEILING INSULATION VALUE TO MATCH ENERGY CALC'S. |
| |
| 11)FOUNDATION MEASUREMENTS ON TYPICAL WALL SECTION |
| PAGE 4/4 DO NOT BALANCE. 16" FOUNDATION WITH 12" BELOW |
| GRADE AND 6" ABOVE = 18" |
| |
| 12)PROVIDE TRUSS ANCHORS WITH FL STATE APPROVAL #'S |
| ON THE SCHEDULE PAGE 3/4OR SUBMIT PRODUCT APPROVAL |
| SHEETS. |
| |
| 13)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| STATE PRODUCT APPROVAL COVER |
| SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| SUBMITTED APPLICATIONS WILL BE DENIED |
| |
| 14)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE |
| PRODUCT APPROVALS |
| A)PROVIDE PRODUCT APPROVALS FOR ROOFING MATERIAL |
| (SHINGLES, ETC.), NON GLAZED REAR DOOR |
| B)TRACO WINDOWS STATE COVER SHEETS (FL# 6738) AND ODL |
| DOORS (MASONITE STEEL DOOR WITH ODL HURRICANE GLAZING |
| 6'-8" FL# 2979) |
| |
| 15)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH ADMINISTRATIVE |
| AMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| FBC RES. = FLORIDA BUILDING CODE |
| RESIDENTIAL 2004 C/W 2006 AMENDMENTS |
| |
| REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF |
| NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY |
| FOR REFERENCE |
| |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |