2007-05-22 08:22:57DENIED;
 1. BOTH THE ASSOCIATES AND THE DESIGN PROFESSIONALS
 STATE LICENSE NUMBERS ARE MISSING FROM THE TITLE BLOCK.
 SEE FLORIDA STATUTES CHAPTER 481 PART II. THE ADDRESS
 OF THE JOB SHOULD ALSO BE IN THE TITLE BLOCK. SEE
 FBC-2004 CHAPTER 1 ADMINISTRATION CODE SECTION
 106.1.1.
 2. THE BACKFLOW PROTECTION BETWEEN THE POTABLE WATER
 AND THE IRRIGATION SYSTEM SHALL BE A REDUCED PRESSURE
 PRINCIPLE BACKFLOW PREVENTOR AND SHALL BE INSTALLED BY
 A LICENSED PLUMBING CONTRACTOR.
 3. PAGE I-2, 3RD AND 4TH FLOOR IRRIGATION PLAN; MORE
 INFORMATION IS REQUIRED ON THE WATER SOURCE. THE
 BUILDING PLUMBING PLANS DON'T SHOW ANY WATER RISERS FOR
 IRRIGATION FOR THE 3RD AND 4TH FLOORS AND THE COLD
 WATER RISERS ARE NOT LARGE ENOUGH. PLEASE ELABORATE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695