Plan Review Notes
Plan Review Notes For Permit 07040544
Permit Number 07040544
Review Stop M
Sequence Number 3
Notes
Date Text
2007-07-03 13:53:28*** PROVISO ***
 1) HAVE AN ENGINEERED DETAIL FOR WALL MOUNTED CONDENSER
 STANDS SHOWING THEY WILL WITHSTAND 140 MPH WINDS, PER
 2004 FBC 1609, SIGNED AND SEALED BY AN ENGINEER, ON THE
 JOB SITE AT TIME OF INSPECTION FOR WPB MECHANICAL
 INSPECTOR (2 COPY'S).
  
 2) 2004 FBC/M 606.2.2 COMMON SUPPLY, RETURN AIR AND
 SUPPLY AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.