Plan Review Notes For Permit 07040544 |
Permit Number |
07040544 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-19 08:57:19 | *** DENIED *** | | 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR DUCTS | | ALSO, SEE 2004 FBC/M 606.2.2, PLEASE CORRECT. | | | | 2) PLEASE SHOW THE SIZES OF THE SUPPLY AIR DUCTS ON THE | | PLANS. | | | | 3) OUTDOOR AIR REQUIRED 250 CFM'S FOR EACH BAY, SEE | | 2004 FBC/M TABLE 403.3 WAREHOUSES REQUIRE 0.05 CFM/SQ. | | FT., 5000 SQ. FT. X 0.05 = 250. PLEASE CORRECT. | | | | 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|