Plan Review Notes
Plan Review Notes For Permit 07040544
Permit Number 07040544
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-19 08:57:19*** DENIED ***
 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR DUCTS
 ALSO, SEE 2004 FBC/M 606.2.2, PLEASE CORRECT.
  
 2) PLEASE SHOW THE SIZES OF THE SUPPLY AIR DUCTS ON THE
 PLANS.
  
 3) OUTDOOR AIR REQUIRED 250 CFM'S FOR EACH BAY, SEE
 2004 FBC/M TABLE 403.3 WAREHOUSES REQUIRE 0.05 CFM/SQ.
 FT., 5000 SQ. FT. X 0.05 = 250. PLEASE CORRECT.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.