2007-06-12 12:59:03BUILDING PLAN REVIEW
 PERMIT:07040505
 ADD: 307 EVERNIA ST.
 CONT: RAYMOND NORDINE
 TEL: (561)655-1912
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)THE ARCHITECT NEEDS TO DATE THE DRAWINGS.
 481.221(2)ALL FINAL CONSTRUCTION DOCUMENTS AND
 INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS, PLANS,
 SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC RECORD
 SHALL BEAR THE SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE DOCUMENT AND THE
 DATE ON WHICH THEY WERE SEALED. THE SIGNATURE, DATE,
 AND SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT
 TO WHICH THEY ARE AFFIXED. SEE ARCHITECTURAL SHEETS.
  
 2) THE DOOR SCHEDULE OF SHEET A-2.01 SHALL INDICATE THE
 DOOR RATING OFDOORS #103.3 AND #103.6 WHIC LEAD TO
 THE EXIT STAIRWAYS.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES MARKETING COST,
 OVERHEAD AND PROFIT EXCLUDING LAND. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  