Plan Review Notes For Permit 07040505 |
Permit Number |
07040505 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-24 11:07:07 | *** DENIED *** | | 1) SEE MECHANICAL PLANS M-1, 8X8 SUPPLY AIR DUCT TO | | HALL 108 WILL NEED A FIRE DAMPER AS THE DUCT IS NOT | | ABOVE THE CEILING IN THE ADJOINING ROOM, AS THE | | BUILDING WAS PERMITTED IN 2001 SEE 2001 FBC/M 607.1.3 | | (4), AND 2001 FBC 412.6. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|