2007-04-24 15:55:29*****DENIED*****
  
  
 1. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2. UNLESS IT IS WALL RECESSED, RELOCATE THE PLACEMENT
 OF THE FIRE EXTINGUISHER FROM THE EXTERIOR WALL OF THE
 MACHINE ROOM AS TO NOT INTRUDING IN THE PATH OF THE
 EXIT ACCESS CORRIDOR.
  
 3. BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR
 FINISH FOR WALLS AND CEILINGSIN THE EXITS, EXIT
 ACCESS CORRIDORS, AND OTHER SPACES AS CLASS A, CLASS B,
 OR CLASS C.
  
 4.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
  
 5.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE
 SCOPE OF WORK BEING CONDUCTED, SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED.
  
 6.ON PLAN SHEET E-2.01 INDICATES AN ACCESS CONTROL
 DOOR.WILL EGRESS THROUGH THIS DOOR BE IMPACTED?
 PLEASE BE ADVISED THAT DOORS IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE EQUIPPED WITH AN APPROVED
 ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM PROVIDED THAT
 THE CRITERIA OF NFPA 101 CHAPTER 7.2.1.6.2 ARE MET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722