2007-04-23 12:33:16 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.1, FBC, SEE
 SPACE CONTROLS FOR LIGHTING ALSO.
  
 2} SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 1
 FLUORESCENT. SUBMIT A FIXTURE SCHEDULE INDICATING
 DENSITY REQUIREMENTS, AND CORRELATE WITH THE ENERGY
 CALCULATIONS.
  
 3} RECEPTACLE CIRCUITS 27 & 29 DO NOT SERVE OFFICE
 106AS LISTED ON SCHEDULE.
  
 4} CIRCUIT 8 THROUGH 36 ON THE RIGHT SIDE OF THE PANEL
 DO NOT LISTS THE ROOMS THE RECEPTACLES ARE SERVING.
 408.4 2005 NEC: EVERY CIRCUIT AND CIRCUIT MODIFICATION
 SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT,
 AND SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 5} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  