Date Text
2007-04-30 08:08:48*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) 8" RETURN AIR DUCT TO THE MASTER SUITE NEEDS TO BE
 10", SEE 2004 FBC/R M1602.4 (C) EXCEPT.
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.