2007-04-27 15:14:52** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE MISSING AIC RATINGS FOR NEW SERVICE
 EQUIPMENT, MAINS, PANELS AND BREAKERS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 110.9
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DEVICES. IF THE SMOKE DEVICES ARE 120V WHICH DETECT,
 SOUND AN ALARM AND ARE WIRED INLINE, THEN THESE DEVICES
 WOULD BE INDICATED AS SA FOR SMOKE ALARMS. PLEASE
 ADJUST.
 PLEASE KNOW IF THEY ARE INDEED SMOKE DETECTORS PLEASE
 INDICATE THE SOUNDING DEVICES.
 PLEASE SEE THE MISSING SMOKE DEVICE REQUIRED AT THE
 FIRST FLOOR LEVEL LEADING TO THE FLOOR ABOVE.
 NFPA-72 11.5.1.1.1, 11.8.3
  
 4) NOTE: PLEASE SEE 210.8A7 WHICH REQUIRES ALL
 RECEPTACLES LOCATED WITHIN 6FT OF SINKS TO BE GFI/GFI
 PROTECTED EVEN IF THEY ARE SINGLE DEDICATED POINT OF
 USE RECEPTACLES. THIS IS REQUIRED FOR 120V DEVICES.
  
 5) NOTE: PLEASE CORRELATE THE RISER AND PLANS AS THE
 PLANS SEEM TO INDICATE A SEPARATE METER AND MAIN
 DISCONNECT.
 106.1.2
  
 6) NOTE:PLEASE SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION. PLAN NOTE MENTIONS FOR RECEPTACLES, WHICH
 CHANGED IN THE 2002 NEC TO REQUIRE ALL OUTLETS IN
 BEDROOM/SLEEPING ROOMS TO REQUIRED AFCI PROTECTION.
 THIS CHANGED IN THE 2002 AND IS THE SAME IN THE 2005.
 ** PLEASE SEE PANEL SCHEDULE(S) ONLY INDICATE ONE AFCI
 PROTECTED CIRCUIT WHICH IS NOT POSSIBLE.
  
 7) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 8) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM CLEARANCE
 REQUIRED FOR DISCONNECTS SHOWN BEHIND A/C CU.
  
 9) NOTE: PLEASE CLARIFY DINING ROOM/BREAKFAST AREA
 CIRCUIT(S) AND THE LIKE AS REQUIRED PER 210.52B1,
 210.11C1, 220.52
  
 10) NOTE: PLEASE SEE SOME ROOMS WHICH INDICATE A
 SWITCH, BUT IT IS NOT SHOWN FEEDING ANYTHING.
 PLEASE ALSO SEE ROOMS WHERE ONLY A J-BOX IS SHOWN FOR A
 FAN WILL REQUIRE A LIGHT FIXTURE OF SOME TYOE FOR FINAL
 OR A SWITCHED RECEPTACLE WILL BE REQUIRED PER 210.70.
 LS 101 7.8
 PLEASE SEE SWITCHES WHICH ARE TIED TO WHAT IS SHOWN A
 3-WAY SWITCHING HOWEVER THE SWITCH IS NOT SHOWN AS A
 3-WAY SWITCH.
  
 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM
 COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT*
 ETC IS NOT ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLES ALONG
 KITCHEN COUNTER SPACES PER 210.52C1-5, 210.8A6.
 PLEASE SEE PENINSULAR AND AREA SEPARATED BY SINK.
  
 13) NOTE: PLEASE SEE THE LIGHT IN CLOSET DOES NOT MEET
 THE MINIMUM CLEARANCES PER 410.8
  
 14) NOTE: PLEASE SEE 422.13 AS THE LOADS SHALL BE SHOWN
 AT 125%.
  
 15) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER
 CURRENT PROTECTION FOR THE AHU #2. THIS IS SHOWN AT
 10KW W/ A 2-POLE 20AMP.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  