2007-04-27 15:14:52 | ** UNSAT ** |
| |
| ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE MISSING AIC RATINGS FOR NEW SERVICE |
| EQUIPMENT, MAINS, PANELS AND BREAKERS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| 110.9 |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| DEVICES. IF THE SMOKE DEVICES ARE 120V WHICH DETECT, |
| SOUND AN ALARM AND ARE WIRED INLINE, THEN THESE DEVICES |
| WOULD BE INDICATED AS SA FOR SMOKE ALARMS. PLEASE |
| ADJUST. |
| PLEASE KNOW IF THEY ARE INDEED SMOKE DETECTORS PLEASE |
| INDICATE THE SOUNDING DEVICES. |
| PLEASE SEE THE MISSING SMOKE DEVICE REQUIRED AT THE |
| FIRST FLOOR LEVEL LEADING TO THE FLOOR ABOVE. |
| NFPA-72 11.5.1.1.1, 11.8.3 |
| |
| 4) NOTE: PLEASE SEE 210.8A7 WHICH REQUIRES ALL |
| RECEPTACLES LOCATED WITHIN 6FT OF SINKS TO BE GFI/GFI |
| PROTECTED EVEN IF THEY ARE SINGLE DEDICATED POINT OF |
| USE RECEPTACLES. THIS IS REQUIRED FOR 120V DEVICES. |
| |
| 5) NOTE: PLEASE CORRELATE THE RISER AND PLANS AS THE |
| PLANS SEEM TO INDICATE A SEPARATE METER AND MAIN |
| DISCONNECT. |
| 106.1.2 |
| |
| 6) NOTE:PLEASE SEE 210.12 FOR REQUIRED ARC FAULT |
| PROTECTION. PLAN NOTE MENTIONS FOR RECEPTACLES, WHICH |
| CHANGED IN THE 2002 NEC TO REQUIRE ALL OUTLETS IN |
| BEDROOM/SLEEPING ROOMS TO REQUIRED AFCI PROTECTION. |
| THIS CHANGED IN THE 2002 AND IS THE SAME IN THE 2005. |
| ** PLEASE SEE PANEL SCHEDULE(S) ONLY INDICATE ONE AFCI |
| PROTECTED CIRCUIT WHICH IS NOT POSSIBLE. |
| |
| 7) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE |
| GROUNDING ELECTRODE SYSTEM PER 250.50. |
| |
| 8) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM CLEARANCE |
| REQUIRED FOR DISCONNECTS SHOWN BEHIND A/C CU. |
| |
| 9) NOTE: PLEASE CLARIFY DINING ROOM/BREAKFAST AREA |
| CIRCUIT(S) AND THE LIKE AS REQUIRED PER 210.52B1, |
| 210.11C1, 220.52 |
| |
| 10) NOTE: PLEASE SEE SOME ROOMS WHICH INDICATE A |
| SWITCH, BUT IT IS NOT SHOWN FEEDING ANYTHING. |
| PLEASE ALSO SEE ROOMS WHERE ONLY A J-BOX IS SHOWN FOR A |
| FAN WILL REQUIRE A LIGHT FIXTURE OF SOME TYOE FOR FINAL |
| OR A SWITCHED RECEPTACLE WILL BE REQUIRED PER 210.70. |
| LS 101 7.8 |
| PLEASE SEE SWITCHES WHICH ARE TIED TO WHAT IS SHOWN A |
| 3-WAY SWITCHING HOWEVER THE SWITCH IS NOT SHOWN AS A |
| 3-WAY SWITCH. |
| |
| 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND |
| PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS |
| AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR |
| EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM |
| COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT* |
| ETC IS NOT ACCEPTABLE. |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLES ALONG |
| KITCHEN COUNTER SPACES PER 210.52C1-5, 210.8A6. |
| PLEASE SEE PENINSULAR AND AREA SEPARATED BY SINK. |
| |
| 13) NOTE: PLEASE SEE THE LIGHT IN CLOSET DOES NOT MEET |
| THE MINIMUM CLEARANCES PER 410.8 |
| |
| 14) NOTE: PLEASE SEE 422.13 AS THE LOADS SHALL BE SHOWN |
| AT 125%. |
| |
| 15) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER |
| CURRENT PROTECTION FOR THE AHU #2. THIS IS SHOWN AT |
| 10KW W/ A 2-POLE 20AMP. |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |