Plan Review Notes
Plan Review Notes For Permit 07040482
Permit Number 07040482
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-24 13:44:48 
  
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE IF THE SERVICE SHOWN ON THE PLAN IS TO BE
 INSTALLED UNDER THIS PERMIT OR IF IT IS EXISTING.
  
 2} THE RISER IS DRAWN AS AN OVERHEAD SERVICE, BUT SAYS
 ITS UNDERGROUND, CORELATE TO INDICATE EXISTING
 CONDITIONS.
  
 3} THE RISER MUST INDICATE CONDUIT AND CONDUCTOR SIZE
 AND TYPE (IF OVERHEAD).
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 5} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 6} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
  
 7} CIRCUITS 21 AND 22HAVE INCORRECT CONDUCTOR SIZES FOR
 THE OCP. SEE 310.16.
  
 8} NOTE #3 REGARDING KITCHEN SINK GFI'S IS INCORRECT.
 SEE 210.8(A)(6). CORRECT THE NOTE.
  
 9} THE NOTE REGARDING " SMOKE DETECTORS" #4, IS
 INCONSISTENT WITH THE CIRCUITING ON THE PANEL SCHEDULE.
 SEE CIRCUIT #26. CORRECT NOTE. ALSO SEE THE DEFINITION
 OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING
 DETECTORS OR ALARMS, TO AVOID CONFUSION IN THE FIELD.
  
 10} NOTE #7 AND THE ARTICLE IT REFERENCES IS NOT IN THE
 2005 NEC. REMOVE OR CORRECT IT..
  
 11} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 12} THE SHEETS OF THE PLANS ARE NOT NUMBERED FOR
 REFERENCE, NUMBER SAME.106.1.3 FBC.
  
 13} THE HALLWAY ON SHEET? REQUIRES A RECEPTACLE TO
 COMPLY WITH 210.52(H).
  
 14} A RECEPTACLE MUST BE ADDED TO THE "NEW BEDROOM" FOR
 COMPLIANCE WITH 210.52(A)(1).
  
 15} THE NOTES ABOVE THE RISER INDICATING 200 AMP
 BREAKER AND 10000 AIC DO NOT CORRELATE WITH THE NOTES
 ON THE BOTTOM OF THE PANEL SCHEDULE AND RISER DIAGRAM
 INDICATING 150 AMPS, AND NOTE #18INDICATING 22000
 AIC..
  
 16} INDICATE WHAT THE 240 VOLT RECEPTACLE IN THE CLOSET
 IS FOR. THERE IS OBVOUSLY A PIECE OF EQIUIPMENT TO BE
 INSTALLED THERE.
  
 17} A TITLE BLOCK IS REQUIRED FOR THE ENGINEER PER 471
 FS. WITH INFORMATION PER 61G15-23.002(2) FAC.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  