Date |
Text |
2007-04-24 13:44:48 | |
| |
| NONCOMPLIANT |
| |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} INDICATE IF THE SERVICE SHOWN ON THE PLAN IS TO BE |
| INSTALLED UNDER THIS PERMIT OR IF IT IS EXISTING. |
| |
| 2} THE RISER IS DRAWN AS AN OVERHEAD SERVICE, BUT SAYS |
| ITS UNDERGROUND, CORELATE TO INDICATE EXISTING |
| CONDITIONS. |
| |
| 3} THE RISER MUST INDICATE CONDUIT AND CONDUCTOR SIZE |
| AND TYPE (IF OVERHEAD). |
| |
| 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 5} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| CHANGE. |
| |
| 6} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| |
| 7} CIRCUITS 21 AND 22HAVE INCORRECT CONDUCTOR SIZES FOR |
| THE OCP. SEE 310.16. |
| |
| 8} NOTE #3 REGARDING KITCHEN SINK GFI'S IS INCORRECT. |
| SEE 210.8(A)(6). CORRECT THE NOTE. |
| |
| 9} THE NOTE REGARDING " SMOKE DETECTORS" #4, IS |
| INCONSISTENT WITH THE CIRCUITING ON THE PANEL SCHEDULE. |
| SEE CIRCUIT #26. CORRECT NOTE. ALSO SEE THE DEFINITION |
| OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING |
| DETECTORS OR ALARMS, TO AVOID CONFUSION IN THE FIELD. |
| |
| 10} NOTE #7 AND THE ARTICLE IT REFERENCES IS NOT IN THE |
| 2005 NEC. REMOVE OR CORRECT IT.. |
| |
| 11} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| |
| 12} THE SHEETS OF THE PLANS ARE NOT NUMBERED FOR |
| REFERENCE, NUMBER SAME.106.1.3 FBC. |
| |
| 13} THE HALLWAY ON SHEET? REQUIRES A RECEPTACLE TO |
| COMPLY WITH 210.52(H). |
| |
| 14} A RECEPTACLE MUST BE ADDED TO THE "NEW BEDROOM" FOR |
| COMPLIANCE WITH 210.52(A)(1). |
| |
| 15} THE NOTES ABOVE THE RISER INDICATING 200 AMP |
| BREAKER AND 10000 AIC DO NOT CORRELATE WITH THE NOTES |
| ON THE BOTTOM OF THE PANEL SCHEDULE AND RISER DIAGRAM |
| INDICATING 150 AMPS, AND NOTE #18INDICATING 22000 |
| AIC.. |
| |
| 16} INDICATE WHAT THE 240 VOLT RECEPTACLE IN THE CLOSET |
| IS FOR. THERE IS OBVOUSLY A PIECE OF EQIUIPMENT TO BE |
| INSTALLED THERE. |
| |
| 17} A TITLE BLOCK IS REQUIRED FOR THE ENGINEER PER 471 |
| FS. WITH INFORMATION PER 61G15-23.002(2) FAC. |
| |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |