2007-05-07 15:30:34DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 3) THE VALUE OF THE JOB HAS BEEN INCREASED TO
 $79,478.00 BASED ON ICC BUILDING VALUATION DATA.
 ADDITIONAL PERMIT FEES ARE DUE.
  
 4) THE ENGINEER'S INFORMATION IS MISSING FROM THE TITLE
 BLOCK. SEE FAC 61G15-23.002.
  
 5) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS. SEE FBC CHAPTER 13.
  
 6) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. SUBMIT A
 SITE PLAN INDICATING THE DISTANCE TO STRUCTURES ON THE
 ADJACENT PROPERTY WHERE THE PROPERTY LINE IS LESS THAN
 SIX FEET FROM THE PROPOSED ADDITION.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT .
  
 7) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 EXCEPTIONS:
 1.OPENINGS SHALL BE PERMITTED IN WALLS THAT ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 2.FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH
 THIS CODE ARE PERMITTED.
  
  
  
 8) PROVIDE AN ELEVATION OF THE RIGHT SIDE OF THE
 STRUCTURE THAT SPECIFIES THE WIND LOAD PRESSURES FOR
 THE WINDOWS.
  
 9) SPECIFY THE WIND LOAD PRESSURES FOR THE DOOR ON THE
 REAR ELEVATION.
  
 10) SHOW COMPLIANCE WITH R905.2.7 UNDERLAYMENT
 APPLICATION.
 FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE),
 UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN THE
 FOLLOWING MANNER. APPLY A 19-INCH (483 MM) STRIP OF
 UNDERLAYMENT FELT PARALLEL WITH AND STARTING AT THE
 EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE. STARTING
 AT THE EAVE, APPLY 36-INCH-WIDE (914 MM) SHEETS OF
 UNDERLAYMENT, OVERLAPPING SUCCESSIVE SHEETS 19 INCHES
 (483 MM), AND FASTENED SUFFICIENTLY TO HOLD IN PLACE.
 FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE) OR GREATER, UNDERLAYMENT
 SHALL BE ONE LAYER APPLIED IN THE FOLLOWING MANNER.
 UNDERLAYMENT SHALL BE APPLIED SHINGLE FASHION, PARALLEL
 TO AND STARTING FROM THE EAVE AND LAPPED 2 INCHES (51
 MM), FASTENED SUFFICIENTLY TO HOLD IN PLACE. END LAPS
 SHALL BE OFFSET BY 6 FEET (1829 MM).
  
 11) SPECIFY THE WINDOW TYPES AND SIZES IN THE FLORIDA
 ROOM.
  
 12) SAFETEY GLAZING IS REQUIRED IN THE NEW BATH ROOM
 WINDOW. SEE FBC R308.
  
 13) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 14) SPECIFY THE THICKNESS OF THE PLYWOOD THAT SHOWN ON
 THE ROOF FRAMING PLAN ON SHEET 2.
  
 15) ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH
 SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE NOTES ON SHEET 2AND
 SHEET 4.
  
 16) PLEASE CLARIFY WHAT 16 " OH MEANS. SEE ROOF FRAMING
 PLAN ON SHEET 2.
  
 17) ON SHEET 3 PLEASE UPDATE STRUCTURAL NOTE 2C FROM
 ASCE 7-98 TO ASCE 7-02.
  
 18) THE STRUCTURAL NOTES ON SHEET 3 SPECIFY EXPOSURE B
 AND THE DESIGN PARAMETERS SPECIFY EXPOSURE C. PLEASE
 CORRECT. NOTE: THE WINDLOAD PRESSURES FOR THE WINDOWS
 ON THE ELEVATIONS ARE FOR EXPOSURE B.
  
 19) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR DOOR, THE
 TRUSS CONNECTORS AND THE LINTELS.
  
 20)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 21)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 22) THE PRODUCT APPROVAL SUBMITTED FOR THE GAF SHINGLES
 HAS BEEN REVISED BY MIAMI-DADE NOA 05-1115.11 WITH FL #
 183-R2. SUBMIT NEW NOA WITH FLORIDA COVERSHEET.
  
 23) SUBMIT AN INSTALLATION SCHEDULE AND KEY PLAN FOR
 THE STORM PANELS. SPECIFY THE MOUNT TYPE, CONNECTION
 TYPE, FASTENERS, FASTENER SPACING, DESIGN PRESSURES,
 ETC.
  