2007-05-01 08:06:09 | BUILDING REVIEW CHECKLIST: |
| 1- SHEET 1 OF 3: |
| A) TYPICAL INTERIOR BEARING WALL: CLARIFY WHY IS |
| THERE A DROP BETWEEN BEDROOM AND LOUNGE AREA? WHICH ONE |
| IS THE LOWEST AREA? SPECIFY FINISH FLOOR AREA IN |
| RELATION TO FINISH GRADE? SEC. 106.1.2 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| B) TYPICAL INTERIOR BEARING WALL DOESN'T MATCH |
| INFORMATION SUBMITTED ON PROPOSED FLOOR PLAN. THERE IS |
| AN EXISTING 4"X6" BEAM WHICH IS NOT SHOWN ON THE |
| SECTION/DETAIL..ALL INFORMATION TO MATCH. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| C) SIZE OF WINDOWS SPECIFIED IN THE BEDROOM DON'T |
| COMPLY WITHSEC. R310 OF 2004 FLORIDA RESIDENTIAL CODE |
| IF USING SINGLE HUNG OR SLIDING WINDOWS.CLEARLY |
| IDENTIFY TYPE OF WINDOW AND REVISE SIZE AS REQUIRED TO |
| COMPLY WITH EGRESS REQUIREMENTS. |
| |
| D) EMERGENCY EGRESS NOTES: UPDATE ALL INFORMATION. |
| SEE SEC. R310 OF 2004 FLORIDA RESIDENTIAL CODE FOR |
| CORRECT CODE SECTIONS TO BE REFERENCED AND REVISE AS |
| REQUIRED. |
| |
| 2- SHEET 2 OF 3: |
| A) FOUNDATION PLAN DOESN'T MATCH SECTION DETAIL FOR |
| INTERIOR BEARING WALL SHOWN ON SHEET 1 OF 3. REVISE AS |
| REQUIRED TO MATCH. |
| |
| B) CONCRETE SLAB NOTESHOWN IN THE FOUNDATION PLAN |
| ISNOT CLEAR.FINISH FLOOR ELEVATION IS NOT CLEAR. |
| IS THIS A NEW CONCRETE SLAB?MISSINGSPECS FOR |
| TERMITE TREATMENT AND SOIL BEARING CAPACITY?. |
| |
| C) PROVIDE ONLY THE DETAILS AND NOTES THAT APPLY TO |
| THIS PROJECT TO EXPEDITE REVIEW PROCESS AND AVOID |
| CONFLICTS OR DELAYS. |
| |
| 3-COMPLETE SCOPE OF WORK IS NOT CLEAR. NEED TO |
| IDENTIFY SPECIFIC WORK TO BE PERFORMED AND VALUATION |
| DECLARED IN THE PERMIT APPLICATION NEED TO BE UPDATED |
| TO REFLECT ALL WORK AND INCLUDE THE ENGINEER FEES AS |
| REQUIRED BY SEC. 108.3 OF CITY AMENDMENTS TO FBC 2004. |
| |
| 4- ENERGY CALCULATIONS: |
| A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| B) REVISE INFORMATION ON TOP OF FORM. EG: OWNER |
| INFORMATION IS INCORRECT AND PROVIDE CORRECT BUILDING |
| ADDRESS. |
| |
| 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 6- AFTER ALL PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD (561)233-5115) TO VERIFY IF |
| IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS |
| AND COPY OF PAID RECEIPT IF IMPACT FEES ARE DUE. |
| |
| 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) SIMPSON CONNECTORS SPECIFIED ON PLANS AND |
| DETAILS. |
| |
| B) WINDOWS AND EXTERIOR DOORS IF REPLACING THEM. |
| ***NOTE: SEE COMMENT REGARDING EGRESS WINDOWS. |
| |
| C) STORM SHUTTERS IF REPLACING WINDOWS. |
| ***NOTE: STORM SHUTTERS REQUIRE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE. |
| |
| 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |