Plan Review Notes
Plan Review Notes For Permit 07040449
Permit Number 07040449
Review Stop B
Sequence Number 1
Notes
Date Text
2007-05-01 08:06:09BUILDING REVIEW CHECKLIST:
 1- SHEET 1 OF 3:
 A) TYPICAL INTERIOR BEARING WALL: CLARIFY WHY IS
 THERE A DROP BETWEEN BEDROOM AND LOUNGE AREA? WHICH ONE
 IS THE LOWEST AREA? SPECIFY FINISH FLOOR AREA IN
 RELATION TO FINISH GRADE? SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 B) TYPICAL INTERIOR BEARING WALL DOESN'T MATCH
 INFORMATION SUBMITTED ON PROPOSED FLOOR PLAN. THERE IS
 AN EXISTING 4"X6" BEAM WHICH IS NOT SHOWN ON THE
 SECTION/DETAIL..ALL INFORMATION TO MATCH. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) SIZE OF WINDOWS SPECIFIED IN THE BEDROOM DON'T
 COMPLY WITHSEC. R310 OF 2004 FLORIDA RESIDENTIAL CODE
 IF USING SINGLE HUNG OR SLIDING WINDOWS.CLEARLY
 IDENTIFY TYPE OF WINDOW AND REVISE SIZE AS REQUIRED TO
 COMPLY WITH EGRESS REQUIREMENTS.
  
 D) EMERGENCY EGRESS NOTES: UPDATE ALL INFORMATION.
 SEE SEC. R310 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 CORRECT CODE SECTIONS TO BE REFERENCED AND REVISE AS
 REQUIRED.
  
 2- SHEET 2 OF 3:
 A) FOUNDATION PLAN DOESN'T MATCH SECTION DETAIL FOR
 INTERIOR BEARING WALL SHOWN ON SHEET 1 OF 3. REVISE AS
 REQUIRED TO MATCH.
  
 B) CONCRETE SLAB NOTESHOWN IN THE FOUNDATION PLAN
 ISNOT CLEAR.FINISH FLOOR ELEVATION IS NOT CLEAR.
 IS THIS A NEW CONCRETE SLAB?MISSINGSPECS FOR
 TERMITE TREATMENT AND SOIL BEARING CAPACITY?.
  
 C) PROVIDE ONLY THE DETAILS AND NOTES THAT APPLY TO
 THIS PROJECT TO EXPEDITE REVIEW PROCESS AND AVOID
 CONFLICTS OR DELAYS.
  
 3-COMPLETE SCOPE OF WORK IS NOT CLEAR. NEED TO
 IDENTIFY SPECIFIC WORK TO BE PERFORMED AND VALUATION
 DECLARED IN THE PERMIT APPLICATION NEED TO BE UPDATED
 TO REFLECT ALL WORK AND INCLUDE THE ENGINEER FEES AS
 REQUIRED BY SEC. 108.3 OF CITY AMENDMENTS TO FBC 2004.
  
 4- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 B) REVISE INFORMATION ON TOP OF FORM. EG: OWNER
 INFORMATION IS INCORRECT AND PROVIDE CORRECT BUILDING
 ADDRESS.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 6- AFTER ALL PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5115) TO VERIFY IF
 IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF IMPACT FEES ARE DUE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SIMPSON CONNECTORS SPECIFIED ON PLANS AND
 DETAILS.
  
 B) WINDOWS AND EXTERIOR DOORS IF REPLACING THEM.
 ***NOTE: SEE COMMENT REGARDING EGRESS WINDOWS.
  
 C) STORM SHUTTERS IF REPLACING WINDOWS.
 ***NOTE: STORM SHUTTERS REQUIRE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  