Plan Review Notes For Permit 07040430 |
Permit Number |
07040430 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-02 15:48:36 | | | | | DENIED | | | | 1)SHUTTER PERMIT APPLICATIONS REQUIRE A KEY PLAN, | | SHUTTER SCHEDULE AND THE DRAWINGS THAT ARE PART OF THE | | PRODUCT APPROVALS CLEARLY MARKED WITH THE INFORMATION | | SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, MOUNTING | | METHOD, ANCHOR TYPE, ETC.) PLEASE SEE THE ATTACHED MEMO | | AND SCHEDULE. PLEASE NOTE THAT YOU HAVE SUPPLIED 2 | | SEPARATE FLORIDA PRODUCT APPROVALS FOR THE SAME PRODUCT | | AND THAT NEITHER OF THEM HAS THE SUPPORTING | | DRAWINGS/DOCUMENTS WITH THEM. FL#320 USES THE | | MIAMI-DADE REPORT AND FL#812 USES AN ENGINEERS | | EVALUATION REPORT. PLEASE CHOOSE ONE OF THESE AND | | SUBMIT 2 COPIES OF THE FL# THAT YOU WISH TO USE AND THE | | COMPLIANCE REPORT THAT BELONGS TO THAT FL#. | | THE REPORT IS EASILY DOWNLOADED BY CLICKING ON THE LINK | | FROM THE PRODUCT APPROVAL THAT IS CHOSEN. | | | | 2)PER 1609.6.1 THE SIMPLIFIED CALCULATION METHOD FOR | | WIND LOADS SHALL NOT BE USED TO DETERMINE WIND | | PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE | | SUBMIT SIGNED AND SEALED ENGINEERS CALCULATIONS. | | | | 3)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS | | REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|