Plan Review Notes
Plan Review Notes For Permit 07040430
Permit Number 07040430
Review Stop B
Sequence Number 1
Notes
Date Text
2007-05-02 15:48:36 
  
 DENIED
  
 1)SHUTTER PERMIT APPLICATIONS REQUIRE A KEY PLAN,
 SHUTTER SCHEDULE AND THE DRAWINGS THAT ARE PART OF THE
 PRODUCT APPROVALS CLEARLY MARKED WITH THE INFORMATION
 SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, MOUNTING
 METHOD, ANCHOR TYPE, ETC.) PLEASE SEE THE ATTACHED MEMO
 AND SCHEDULE. PLEASE NOTE THAT YOU HAVE SUPPLIED 2
 SEPARATE FLORIDA PRODUCT APPROVALS FOR THE SAME PRODUCT
 AND THAT NEITHER OF THEM HAS THE SUPPORTING
 DRAWINGS/DOCUMENTS WITH THEM. FL#320 USES THE
 MIAMI-DADE REPORT AND FL#812 USES AN ENGINEERS
 EVALUATION REPORT. PLEASE CHOOSE ONE OF THESE AND
 SUBMIT 2 COPIES OF THE FL# THAT YOU WISH TO USE AND THE
 COMPLIANCE REPORT THAT BELONGS TO THAT FL#.
 THE REPORT IS EASILY DOWNLOADED BY CLICKING ON THE LINK
 FROM THE PRODUCT APPROVAL THAT IS CHOSEN.
  
 2)PER 1609.6.1 THE SIMPLIFIED CALCULATION METHOD FOR
 WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE
 SUBMIT SIGNED AND SEALED ENGINEERS CALCULATIONS.
  
 3)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS
 REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW