2007-06-09 05:50:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. THE FOLLOWING ITEMS NEED CLARIFICATION:
  
 1. TYPE OF GAS, (LP OR NATURAL). THE APPLICATION
 INDICATES NATURAL GAS, BUT THE MANUF. SPECIFICATION
 SHEETS ARE INDICATING PROPANE. PLEASE CLARIFY.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). THE RISER DIAGRAM INDICATES 500,000 BTU, BUT
 THE FUEL CONSUMPTION FOR NATURAL GAS IS 560 CU FT/HR
 BTU AT 100% RATED LOAD, AND 222.3 CU FT/HR FOR PROPANE.
 PLEASE CLARIFY.
  
 B. IF LP GAS THE FOLLOWING COMMENTS APPLY:
  
 3. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 4. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  