2007-06-09 05:50:09 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| A. THE FOLLOWING ITEMS NEED CLARIFICATION: |
| |
| 1. TYPE OF GAS, (LP OR NATURAL). THE APPLICATION |
| INDICATES NATURAL GAS, BUT THE MANUF. SPECIFICATION |
| SHEETS ARE INDICATING PROPANE. PLEASE CLARIFY. |
| |
| 2. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). THE RISER DIAGRAM INDICATES 500,000 BTU, BUT |
| THE FUEL CONSUMPTION FOR NATURAL GAS IS 560 CU FT/HR |
| BTU AT 100% RATED LOAD, AND 222.3 CU FT/HR FOR PROPANE. |
| PLEASE CLARIFY. |
| |
| B. IF LP GAS THE FOLLOWING COMMENTS APPLY: |
| |
| 3. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| 4. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |