Plan Review Notes
Plan Review Notes For Permit 07040404
Permit Number 07040404
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-30 11:45:27** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
  
 2) NOTE: PLEASE VERIFY SYSTEM BEING INSTALLED AND
 PROPOSED. PLEASE SEE THE GENERATOR LOAD CALCULATIONS
 AND SPECIFICATIONS INDICATE THIS UNIT AS 120/240 SINGLE
 PHASE, AND THE PLANS INDICATE THE EQUIPMENT/PANEL BEING
 120/208V.
 PLEASE ALSO SEE THAT PART OF THE RISER SHOWS THIS
 SERVICE AS THREE PHASE.?
 FBC 106 .1.2
  
 3) NOTE: PLEASE SEE THE RISER STILL SEEMS TO SHOW A
 CONNECTION FROM THE GUTTER TO THE SAME PANEL WHICH IS
 BEING FED FROM THE GENERATOR?
 PLEASE CLARIFY RISER AS SHOWN AS THE EXISTING
 CONNECTION FROM GUTTER WOULD BE REQUIRED TO BE REMOVED
 INCLUDING CONDUIT.
 PLEASE CLARIFY RISER AS SHOWN WITH THE FEED FROM FPL.
 DOES THIS COME THROUGH THE METER? IS THIS A 600AMP
 METER/ OR CT.
 FBC 106.1.2,
 NEC 215.5
  
 4) NOTE: PLEASE CLARIFY THE LOAD CALCULATIONS AS SHOWN.
 PLEASE SEE THESE MENTION APARTMENT LOADS, HOWEVER THE
 LOADS ARE NOT COMPLETE FOR APARTMENTS.
 PLEASE SEE THE LOADS MUST BE BASED ON THE NEC. 220
 (2005 NEC).
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATION SHEET
 INDICATES THE GENERATOR BREAKERAT 200AMPS, THE RISER
 SHOWS THIS AS 150AMPS, AND THE SPECS INDICATES 175AMP?
 PLEASE COORDINATE ALL, AT THIS TIME THE SIZES OF
 CONDUCTORS ETC CAN NOT BE VERIFIED.
 240.4, 310.16 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE SPECS SUBMITTED FOR THE ATS
 DOES NOT INDICATE A DISCONNECTING MEANS FOR THE
 LINE/NORMAL SIDE AND A BREAKER/DISCONNECT FOR THE
 GENERATOR/EM SIDE?
 PLEASE REVISE SPECS OR RISER TO INCLUDE A DISCONNECTING
 MEANS AT THE SERVICE LOCATION.
 225.31-225.39.
 ** PLEASE KNOW, AS ZONING COMMENTS WILL MOST LIKELY
 REQUIRE THIS UNIT TO BE IN AN ENCLOSURE THE BREAKER ON
 THE GENERATOR MAY NOT BE USED.
  
 7) NOTE: PLEASE PROVIDE ALL ELECTRICAL EQUIPMENT ON THE
 PLAN LAYOUT SHEET.
 FBC 106.1.2
 LOCATIONS NEED TO BE VERIFIED FOR 230, 225 ETC.
  
 8) NOTE: PLEASE SEE THE SPECIFICATIONS INDICATES THIS
 AS BEING CONNECTED TO A PROPANE TANK, YET THE GAS
 PERMIT APPLICATION MENTIONS THIS WILL BE A NATURAL GAS
 UNIT?
 PLEASE SEE COMMENTS FROM PLUMBING.
  
 9) NOTE: PLEASE SEE THE NOC SUBMITTED AS EXPIRED PER FS
 713.13(2).
 PLEASE SEE THE NOC WILL BE REQUIRED TO BE RE-RECORD
 BEFORE PICKING UP THE PERMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-27 17:00:40PLANS REMOVED FROM INCOMING/TABLE IN ELEC FOR REVIEW.